A cable short-circuit rating combines current, duration and temperature conditions. A one-second rating is a thermal withstand reference, not continuous ampacity. Compare the fault energy delivered before protection clears with the withstand of the relevant conductor, screen or sheath and connections. Mechanical restraint requires a separate check.

Read the seconds beside the kiloamperes
A datasheet’s short-circuit current depends on material, conductor area, starting temperature, permitted final temperature and calculation method. Duration belongs beside the current: a high current interrupted quickly can produce less heating than a smaller current that persists.
The network study establishes the available fault current. The selected cable has a defined withstand. Between those two, protection determines the exposure through detection, operation and interruption. Our preference is to keep those three records together rather than compare the cable and switchgear using a single kA figure.
One conductor, two clearing times
Consider an illustrative adiabatic calculation for a 120 mm² conductor with an assumed coefficient k of 143 A·√s/mm². In a project, k follows the material and initial/final temperature basis; it is not a universal value for every copper cable.
I = kS / √t, where I is the equivalent thermal current in amperes, S is area in mm² and t is duration in seconds. Equivalently, compare I²t with k²S².
| Thermal comparison | 1.0 second | 0.2 second |
|---|---|---|
| Calculated permissible current | 17.16 kA | 38.37 kA |
| Example fault current | 20 kA | 20 kA |
| Fault energy, I²t | 400 million A²s | 80 million A²s |
| Conductor limit, k²S² | 294.47 million A²s | 294.47 million A²s |
| Result for this assumed conductor | Above the thermal limit | Below the thermal limit |

At 20 kA, the simplified maximum duration is (17.16 / 20)², approximately 0.736 s. That calculation explains the relationship; it is not a protective-device setting. Apply the valid calculation range and the actual device and cable-system conditions.
The conductor’s continuous current rating has not changed between the two columns. Continuous service depends on sustained losses and heat dissipation; short-circuit withstand concerns a short event from a defined initial temperature.
Use the actual clearing duty, not just the relay delay
The time used in the thermal check should describe the relevant total fault-clearing duty. A relay delay alone may omit other parts of the operating and interruption sequence. Backup protection can introduce a different exposure that also needs assessment.
For a changing current waveform, thermal duty is represented by the integral of current squared over time. A simple I²t check uses an appropriate equivalent current for that interval. For a current-limiting fuse or circuit-breaker, use the applicable manufacturer’s let-through energy data, with its specified voltage and prospective fault conditions.
IEC 60909 addresses AC network short-circuit calculations. IEC 60949 addresses permissible cable thermal current, starting with an adiabatic result and accounting for non-adiabatic heating through a modifying factor. Follow the method and edition adopted by the project; a short-time approximation should remain within its applicable conditions.
The official thermal calculation framework explains that approach. It describes a method, rather than certifying a particular cable.
Check the conductor and the metallic return path separately
An earth fault on a screened MV circuit can involve the metallic screen and its bonding system. The network and earthing arrangement determine the current assigned to that path. Screen duty should therefore come from the system study rather than from the cable’s normal load current.

A designation such as 1×240/25 distinguishes a 240 mm² phase conductor from a 25 mm² metallic screen. They have different areas and functions. Screen material, connections, bonding leads and accessories each belong in the fault-path assessment.
IEC 60986 addresses temperature limits for its covered MV range, considering insulating and other cable materials, connections and accessories. Retain that construction context when selecting the calculation assumptions.
The XWA N2XSY screened MV cable page separates conductor and screen information. For an LV feeder, N2XY XLPE power cable provides the corresponding construction context. Neither product name replaces the circuit’s thermal and protective-path checks.
Thermal withstand and peak-force restraint answer different questions
Fault current also creates electromagnetic forces. Cleats, supports, bends and termination restraints need assessment for the relevant peak current and cable arrangement. An RMS thermal rating in kA for a stated duration is not a mechanical restraint rating.
On large single-core circuits, formation and the complete support load path become especially important. Our MV cable restraint guide explains the installation side of that assessment.
Keeping the two checks distinct improves the specification: one controls permissible heating, while the other addresses the forces transmitted through the installed system.
Build a fault-duty record that can follow the cable schedule
Record the fault current at the relevant location, total clearing time or let-through energy, conductor and screen/sheath construction, temperature basis and calculation method. Add the connection, accessory and restraint requirements. Those conditions make a rating meaningful and allow alternatives to be compared consistently.