Power Cable Size Calculator
Estimate the required conductor size based on load, voltage, cable length, conductor material and allowable voltage drop.
| Design Check | Required Size | Status |
|---|---|---|
| Current Carrying Capacity | — | PASS |
| Voltage Drop | — | PASS |
A cable size calculation checks both current-carrying capacity and voltage drop. This calculator estimates a metric conductor cross-section from the electrical load, route length, material and selected factors. Use the explanations below to understand which check controls the result and what the selected size means for a power-cable specification.
Which inputs change the required cable size?
Start with the circuit rather than a preferred conductor size. A short industrial feeder and a long underground run can carry the same current yet need different cross-sections. The first may be governed by heating; the second may require a larger conductor to limit voltage drop.
| Input | What to enter | Why it matters |
|---|---|---|
| Electrical system and voltage | Single-phase AC, balanced three-phase AC or DC. For three-phase, enter line-to-line voltage. | The system determines the load-current and voltage-drop calculation. |
| Load | Amperes, electrical input power in kW, or AC apparent power in kVA. | These are different quantities. Motor shaft-output kW requires an efficiency adjustment before it represents electrical input power. |
| Power factor | The operating power factor for an AC load entered in kW. | At the same kW and voltage, a lower power factor means a higher current. |
| One-way length | The routed distance from supply to load, in metres. | The calculator already applies its circuit factor; entering an out-and-back distance would count the return path twice. |
| Conductor and insulation | Copper or aluminium; XLPE or PVC insulation. | The tool selects the corresponding reference ampacity table and conductor resistance model. |
| Derating and design load factors | A combined derating factor above zero and up to 1; a design load multiplier of at least 1. | Derating reduces the available table rating. The design multiplier increases the current used for the ampacity check. |
| Voltage-drop limit | The allowance allocated to this circuit by the project design. | A limit for a complete installation may need to be shared between upstream and downstream circuits. |
| Parallel cables per phase | The number of parallel conductor paths planned for each phase or pole. | The estimate divides current equally between paths. Actual current sharing, grouping and terminations need the corresponding circuit design. |
In practice, a meaningful derating factor starts with a suitable installation rating and its reference conditions. A single multiplier cannot turn a generic table into a detailed model of every tray, duct or buried route.
From kW or kVA to cable current
For electrical input power P in kW, current I in amperes and voltage U in volts, the calculator uses:
- Single-phase AC: I = 1000 × P / (U × PF)
- Balanced three-phase AC: I = 1000 × P / (√3 × U × PF)
- DC: I = 1000 × P / U
For AC apparent power S in kVA, omit PF: I = 1000 × S / U for single-phase, or I = 1000 × S / (√3 × U) for balanced three-phase. For DC, use amperes or kW. If operating current is already known, entering amperes avoids a separate conversion.
How the two sizing checks work together
The tool finds the first listed metric size whose reference ampacity, multiplied by the derating factor, covers the design current per cable. Separately, it finds the first size that meets the voltage-drop limit at the load current per cable. The larger of these two sizes becomes the preliminary recommendation.
Design current = load current × design load factor
Required reference ampacity per cable = design current / (parallel paths × derating factor)
A load factor of 1.25 and derating factor of 0.80 therefore do different jobs. They should represent deliberate design assumptions, rather than two interchangeable safety margins.
Worked example: a 75 kW, 400 V three-phase feeder
Consider an illustrative balanced load of 75 kW electrical input at 400 V and power factor 0.85. Select copper, XLPE insulation, one cable per phase, a 1.25 design load factor, 0.80 derating factor and a 3% voltage-drop allowance for this example.
Load current = 75,000 / (√3 × 400 × 0.85) ≈ 127.4 A
Design current ≈ 159.2 A
Required reference ampacity ≈ 159.2 / 0.80 = 199.0 A
In this calculator’s built-in copper/XLPE table, 35 mm² has a reference rating of 167 A and 50 mm² has 202 A. After applying 0.80, those become 133.6 A and 161.6 A respectively. The current check therefore selects 50 mm².
| One-way length | Size from current check | Size from voltage-drop check | Tool recommendation | Calculated drop |
|---|---|---|---|---|
| 70 m | 50 mm² | 35 mm² | 50 mm² | About 1.74% |
| 200 m | 50 mm² | 95 mm² | 95 mm² | About 2.61% |
These are reproducible outputs of the tool’s simplified model, not installation ratings for a particular manufactured cable. The useful insight is the change in the governing condition: the shorter route is controlled by current capacity, while the longer route is controlled by voltage drop. The 3% allowance is an example input, not a universal rule.
What the result includes
The recommended mm² value is the nominal cross-sectional area of each selected conductor, not the cable’s overall diameter. A result such as two parallel 240 mm² conductors per phase describes two separate paths for that phase; it does not specify core count, neutral size, armour, sheath or cable voltage rating.
The calculation model
- Ampacity: fixed copper/aluminium and XLPE/PVC reference tables, adjusted by the entered derating factor. The interface does not select a documented installation method or calculate soil heat transfer.
- Voltage drop: a resistance-only estimate using R = ρ/A, with ρ set to 0.0225 for copper or 0.036 for aluminium in Ω·mm²/m. The tool uses ΔU = 2ILρ/A for single-phase/DC and ΔU = √3ILρ/A for balanced three-phase, then ΔU% = 100ΔU/U.
- Design margin: the load multiplier affects the ampacity check. Voltage drop is calculated at the entered load current, divided between the selected parallel paths.
- Metric output: the search covers the listed sizes from 1.5 to 1000 mm² per conductor. Approximate AWG/kcmil labels are area comparisons, not automatic replacement sizes.
For AC circuits, the model does not separately include reactance or the R cosφ + X sinφ impedance expression. It also does not solve motor starting, harmonics, unequal parallel sharing, short-circuit withstand or protective-device coordination. Final circuit selection brings these checks together with the applicable installation rules and product data.
The official wiring-system publication scope describes the subject covered by IEC 60364-5-52. The online estimate is not a claim that a particular installation complies with that standard.
Turn the conductor size into a cable specification
A useful next step is to connect the electrical estimate with the physical route. Conductor material, voltage rating, core arrangement, screening, armour and sheath determine which cable construction fits the project. For relevant construction options, explore XWA’s low-voltage power cables and aluminium power cables.
If the drawing uses AWG or MCM rather than mm², the AWG, kcmil and metric conductor-size guide explains the units and conversion. For a known cross-section, the voltage-drop calculator provides a separate way to examine route drop.
Have a feeder schedule or an existing cable specification? Share it with XWA to discuss the cable construction, quantities and project supply requirements.
Cable sizing questions
What cable size is needed for a given kW load?
kW alone is insufficient. Supply voltage, phase arrangement and AC power factor establish current; length, material, installation rating and allowable voltage drop influence the conductor size. Use electrical input power, rather than motor shaft-output power without an efficiency adjustment.
Why does a longer cable need a larger cross-section?
Increasing length increases circuit resistance in this model. A larger conductor reduces that resistance, which can bring voltage drop within the selected allowance even when a smaller conductor already passes the current check.
Does XLPE insulation always mean a smaller cable?
The tool uses different reference ampacity tables for XLPE and PVC. Actual selection also depends on installation conditions, termination temperature limits and voltage drop. A different insulation option may leave the recommended section unchanged when voltage drop governs.
Is the nearest AWG or kcmil value an approved substitute?
No. The displayed value compares conductor areas. A substitute cable needs its own applicable conductor, product and installation requirements checked, including resistance, current rating and termination compatibility.