XLPE/SWA/LSZH Cable

هوا باور & كابل | ARMOURED HALOGEN-FREE CONSTRUCTIONS

XLPE/SWA/LSZH Cable combines cross-linked polyethylene insulation, steel wire armour and a low-smoke zero-halogen outer sheath. It is a construction family for fixed power routes where mechanical protection and specified smoke and gas performance are both important.

In enclosed power routes, smoke and combustion gases deserve attention alongside mechanical protection. Our recommendation is to treat the insulation, الحشو, bedding and sheath as one material system, with the required smoke, gas and flame tests specified together. Rated voltage and metallic screens then define the electrical construction for the circuit.

Discuss an LSZH armoured cable project
العزل
XLPE
Mechanical layer
درع من الأسلاك الفولاذية
الغلاف الخارجي
Low smoke, zero halogen

XLPE/SWA/LSZH layer combinations

An unscreened construction is CU/XLPE/LSZH/SWA/LSZH: copper conductor, العزل XLPE, halogen-free bedding, wire armour and halogen-free sheath. Whole-cable smoke and halogen performance depends on the bedding, fillers and other non-metallic components as well as the outer sheath.

Unscreened distribution construction

Multicore LV designs combine the insulated core assembly with bedding, SWA and an outer sheath. Equal-section cores, reduced neutrals and protective cores are separate circuit arrangements; conductor material and core count remain part of the specification.

Screened MV construction

A screened MV example is CU/XLPE/CTS/LSZH/SWA/LSZH. Semiconductive layers control the electric field, the copper tape screen performs the specified electrical duty, and steel wire armour protects the assembly mechanically. Copper-wire screening is another option.

Cut end of a four-core copper cable showing coloured core insulation and a ring of armour wires
Four-core cable cross-section with copper conductors and steel wire armour.

Screened three-core cable construction

Three-core XLPE/SWA/LSZH cable illustration showing copper conductors, العزل, شاشات معدنية, inner bedding, steel wire armour and outer sheath
Screened three-core XLPE/SWA/LSZH construction. Illustration – not to scale.
ElementWhat it contributesWhat the short name leaves open
Copper or aluminium conductorCarries circuit currentمادة, فصل, shape, section and neutral/earth arrangement.
العزل XLPESeparates conductors electricallyالجهد المقنن, insulation thickness and any field-control layers.
Fillers and beddingSupports the laid-up cores and armourCompound, tape system and their contribution to declared fire properties.
درع من الأسلاك الفولاذيةMechanical protection around a multicore assemblyWire dimensions, corrosion protection and bonding/protective-conductor assessment.
LSZH الغلاف الخارجيSpecified smoke and halogen-related performanceCompound grade, fire tests, weather resistance and environmental limits.

SWA is commonly used around multicore AC assemblies. Single-core AC circuits generally use non-magnetic armour, such as aluminium wire armour, to control magnetic losses and heating.

Low-smoke materials and fire-performance requirements

An LSZH cable design combines the insulation, الحشو, الفراش, tapes and outer sheath with the specified smoke and combustion-gas requirements. This material selection is particularly relevant to enclosed power routes and occupied buildings.

PropertyRelevant test frameworkMeaning for a project
Smoke emissionاللجنة الانتخابية المستقلة 61034-2Assesses smoke under defined cable-burning conditions; not a promise of zero smoke.
Halogen acid gasاللجنة الانتخابية المستقلة 60754-1Tests gases from cable materials against the specified requirements.
Acidity and conductivityاللجنة الانتخابية المستقلة 60754-2Assesses gas-related acidity/conductivity; separate from optical smoke measurement.
انتشار اللهبApplicable IEC 60332 امتحانSingle-cable and bunched-cable tests are different scopes.
Circuit integrity in fireApplicable fire-resistance specificationRequires a separately qualified design and test; it is not established by LSZH or SWA.

ال official smoke-test procedure explains how smoke emission is measured under IEC 61034-2. The project specification sets the required smoke, gas and flame-spread performance; circuit integrity during fire is a separate tested requirement.

Voltage and screens define each power-cable design

Construction scopeLayer distinctionTechnical information carried by its datasheet
LV armoured power cableXLPE-insulated core assembly, halogen-free bedding, SWA and LSZH sheathالجهد االكهربى, core functions, conductor class and shape, أبعاد, installation limits and fire declarations.
MV screened armoured power cableAdditional semiconductive layers and metallic screening matched to the voltageScreen construction and fault duty, نظام العزل, مُكَمِّلات, bonding and project installation rating.
Higher-voltage project requestA complete cable-system design, not an LV construction scaled upApplicable system standard, metallic sheath/screen, خسائر, الترابط, accessories and qualification evidence.

The dimensions below cover a four-core 0.6/1 kV construction. Medium-voltage cable systems use additional electrical screens and voltage-specific insulation, with their own dimensions and accessories. Higher-voltage systems require a dedicated cable-system design.

Large-section reference: four-core copper, 0.6/1 كيلو فولت

البيانات المرجعية الموصى بها: four equal-section class 2 copper cores, العزل XLPE, LSZH bedding, SWA and LSZH sheath. These published reference dimensions support preliminary planning; final supply dimensions follow the agreed XWA datasheet.

Cores × section (مم²)الأعلى. DC resistance at 20°C (أوم / كم)العزل (مم)الغلاف الخارجي (مم)القطر الكلي (مم)تقريبا. كتلة (كجم/كم)
4 × 500.3871.02.134.53400
4 × 700.2681.12.239.64727
4 × 950.1931.12.444.06567
4 × 1200.1531.22.649.97748
4 × 1500.1241.42.754.39609
4 × 2400.07541.73.166.114496

Insulation and sheath thicknesses are nominal in this reference. Other conductor shapes, bedding compounds and armour dimensions produce different overall diameters and weights even at the same nominal section. Three-core, five-core and reduced-neutral designs need their own rows.

Current rating is calculated for the installation method, loaded cores, درجة الحرارة المحيطة, التجمع وظروف التربة. The project datasheet and route calculation establish the circuit rating.

Finished diameter determines gland entry and termination space. الفراش, sheath and armour dimensions also affect mass and bending behaviour, so accessory selection follows the finished cable dimensions.

Mechanical protection on routes with smoke and gas requirements

This construction is used for fixed power distribution in industrial facilities, transport infrastructure, plant rooms and building-service routes where mechanical protection and specified smoke and gas performance are required.

Indoor-to-outdoor routes combine fire-performance requirements with exposure conditions. Sheath compound selection addresses UV, رُطُوبَة, hydrocarbons, chemicals and installation temperature for the actual route.

For wet routes, dedicated water-blocking layers can be specified alongside mechanical armour. Moving, suspended and subsea applications require constructions designed for those mechanical and environmental duties.

XWA cable manufacturing and project supply

قوة XWA & Cable manufactures power cables in Henan, الصين. معالجة الموصل, قذف العزل, armouring and sheathing are part of our cable factory operations.

XWA supports cable manufacturing to project drawings and cable schedules. The agreed LSZH design brings together the electrical rating, non-metallic materials and specified smoke, halogen and flame tests.

Delivery length is part of the configuration. The finished diameter and mass establish a starting point for drum dimensions, handling equipment and route pulling arrangements; gross drum weight includes more than cable conductor weight.

بكرات كابلات فولاذية كبيرة مع كابل أسود ملفوف على أرضية المصنع
بكرات فولاذية مزودة بكابل ملفوف للتعامل وتخطيط الأسطوانة.

Questions about the LSZH armoured structure

What does XLPE/SWA/LSZH mean?

XLPE identifies the insulation, SWA the steel wire armour and LSZH the low-smoke zero-halogen outer-sheath family. موصل, الفراش, شاشات, voltage and test requirements complete the specification.

Is CU/XLPE/LSZH/SWA/LSZH a separate model name?

It describes the layers from the centre outwards: copper conductor, العزل XLPE, LSZH bedding, steel wire armour and LSZH outer sheath.

Can this structure be used for medium voltage?

نعم. Screened MV constructions combine XLPE insulation, voltage-appropriate semiconductive layers, a metallic screen, armour and an LSZH sheath system. Screen fault duty, dimensions and accessories are selected for the voltage rating.

Does an LSZH outer sheath make PVC bedding halogen-free?

PVC bedding contains halogen. A whole-cable halogen-free specification addresses the fillers, الفراش, tapes and sheath together, with the corresponding material and test requirements.

Is XLPE/SWA/LSZH cable fire-resistant?

LSZH describes smoke and halogen-related properties. Continued circuit operation during fire requires a fire-resistant construction and a corresponding circuit-integrity test.

Can steel wire armour replace a copper screen?

Steel wire armour provides mechanical protection; a copper screen performs the specified electrical duty. A screened MV armoured cable contains both layers.