N2XS(ف)2والكابل

N2XS(ف)2والكابل is a screened single-core copper power cable with XLPE insulation, شاشة الأسلاك النحاسية, longitudinal water-blocking components and a PE outer sheath. It is intended for fixed medium-voltage distribution rather than flexible trailing service.

The copper conductor carries load current; the surrounding screen performs a separate electrical duty. Industrial feeders, substation circuits and underground networks use this construction where the voltage, bonding arrangement and route conditions match the cable-system design.

Copper single-core XLPE cable cutaway showing the conductor, copper wire screen and black PE sheath
Single-core copper construction with metallic screening. Illustration, not to scale.

بناء

موصل
Stranded copper
العزل
XLPE between semiconductive conductor and insulation screens
Screen region
Copper wires and tape; longitudinal water-blocking components
الغلاف الخارجي
Black PE; no armour in the reference construction

صفات

Reference voltage
12/20 (24) كيلو فولت
Core configuration
أحادي النواة; separate conductor and screen areas
Thermal reference
90°C maximum operating conductor temperature in the source design
Standard context
عالية الدقة 620 / دين فد 0276-620; agreed project requirements

N2XS(ف)2Y for Fixed Power Distribution

الجهد االكهربى, conductor/screen size and route conditions define the project configuration.

طلب عرض أسعار

N2XS(ف)2البيانات الفنية للكابل Y

Recommended reference data. Final dimensions and ratings follow the approved project configuration; the selected rows are not a confirmed XWA production range.

حجم الكابل
(مم²)
مقاومة العاصمة
20درجة مئوية (أوم / كم)
العزل
(مم)
تقريبا. ل
(مم)
تقريبا. كتلة
(كجم/كم)
Air
(أ)
Ground
(أ)
1 س 95/160.1935.5321580361323
1 س 150/250.1245.5352212470409
1 س 240/250.0755.5393181634532
1 س 300/250.0605.5423851724599
1 س 400/350.0475.5444795829671
1 س 500/350.0375.5475873953754

Copper single-core N2XS(ف)2ي, 12/20 كيلو فولت, copper wire screen and PE sheath. The listed dimensions, mass and current ratings apply to this reference construction and the installation conditions below.

Ampacity basis: one circuit in touching trefoil, screens solidly bonded; air 30°C without direct sun; ground 20°C at 0.7 m depth. Source assumptions include 1.0 K·m/W wet soil and 2.5 K·m/W dry soil, with no additional heat sources. Reference conductor limit: 90درجة مئوية.

موصل النحاس, metallic screen and the (ف) تعيين

In a reference 1×240/25 بناء, 240 mm² belongs to the phase conductor and 25 mm² to the metallic screen. Screen fault-current duty, protection clearing time and accessory connections are separate from continuous conductor ampacity.

ال (ف) construction uses water-blocking components to limit moisture propagation along the cable. N2XS(فلوريدا)2Y adds a laminated metallic barrier beneath the PE sheath for radial moisture protection. A PE sheath alone does not provide the same barrier construction.

Single-core copper cable diagram explaining a 240 mm2 conductor and a separately specified 25 mm2 metallic screen
The conductor area and screen area are separate specification entries.
Comparison of ordinary PE sheath, longitudinal water blocking and a longitudinal plus radial barrier construction
ال (ف) و (فلوريدا) variants are different constructions, not interchangeable spelling choices.

Applications and Installation Conditions

Fixed industrial power intake, substation feeders and underground distribution can use this screened construction. Unarmoured cable still needs route-specific mechanical protection. Indoor fire requirements, water exposure and accessory interfaces must match the stated design; the model name alone does not establish submarine suitability.

The test schedule distinguishes conductor resistance, insulation tests and sheath checks from the evidence for the (ف) حاجز الماء. Screen connections and accessory interfaces also belong to the cable-system specification. The IEC publication scope explains the fixed-installation framework; certification requires separate evidence.

N2XS(ف)2Y and Related Constructions

نموذجMain difference
N2XS2Y cableموصل النحاس, XLPE insulation and PE sheath; longitudinal water blocking is not specified by the N2XS2Y designation.
N2XSY cableCopper screened MV cable with PVC outer sheath.
N2XS(فلوريدا)2يCombines longitudinal water blocking with a laminated metallic barrier beneath the PE sheath for radial moisture protection.

N2XS(ف)2الأسئلة الشائعة حول كابل Y

Are N2XS(ف)2Y and N2XS2Y interchangeable?

ليس تلقائيا. ال (ف) construction includes longitudinal water blocking; an ordinary PE-sheathed cable should not be assumed to provide the same water-penetration performance.

What does 1×240/25 identify?

One 240 mm² phase conductor and a separately specified 25 mm² metallic screen in the reference construction. The screen is not another power core.

Can the displayed ampacity be used for ducts?

Not directly. The table uses the stated trefoil, bonding and thermal conditions. القنوات, surrounding materials and grouped circuits require the applicable current-rating calculation.