N2XS(فلوريدا)2والكابل

N2XS(فلوريدا)2والكابل is a single-core copper medium-voltage power cable with XLPE insulation, شاشة الأسلاك النحاسية, longitudinal water blocking and a laminated radial moisture barrier beneath its PE sheath.

Its two moisture-control features perform different jobs: swellable components restrict water travel along the screened core, while the metal/polymer laminate reduces radial moisture ingress. The construction suits fixed distribution circuits where both functions form part of the specified cable design.

Illustrated straight copper single-core cable with copper wire screen, thin metallic moisture barrier and black PE sheath
N2XS(فلوريدا)2Y construction concept: copper core, screened XLPE and a laminated barrier beneath the PE sheath. Not to scale.

بناء

موصل
Stranded copper phase conductor
العزل
XLPE with inner and outer semiconductive screens
Screen region
Copper wires, copper tape and water-blocking components
Outer layers
Aluminium/polymer laminate and black PE sheath; غير مدرع

صفات

Reference voltage
12/20 (24) kV for the data below
Moisture protection
Longitudinal blocking plus a radial barrier
خدمة
Fixed distribution, industrial feeders and substation circuits
Standard context
عالية الدقة 620 / دين فد 0276-620; اللجنة الانتخابية المستقلة 60502-2 متطلبات المشروع

N2XS(فلوريدا)2Y Project Enquiries

Discuss the voltage, conductor/screen combination and specified moisture-barrier design with XWA.

طلب عرض أسعار

N2XS(فلوريدا)2البيانات الفنية للكابل Y

البيانات المرجعية الموصى بها: the stated 12/20 kV copper single-core construction. Published dimensions and ratings support preliminary planning; final supply data follows the approved XWA specification and project calculation.

مقاس
(مم²)
مقاومة العاصمة
20درجة مئوية (أوم / كم)
العزل
(مم)
تقريبا. ل
(مم)
تقريبا. كتلة
(كجم/كم)
هواء, ثلاثي الفصوص
(أ)
أرضي, ثلاثي الفصوص
(أ)
1 س 95/160.1935.5331675361323
1 س 150/250.1245.5362320470409
1 س 240/250.0755.5403303634532
1 س 300/250.0605.5433978724599
1 س 400/350.0475.5454925829671
1 س 500/350.0375.5496006953754

The first size is the phase-conductor area; the second is the metallic-screen area. Nominal PE sheath thickness in this reference is 2.5 مم. Diameter and mass are approximate.

Current-rating reference: one circuit in touching trefoil; screens solidly bonded; الهواء 30 درجة مئوية بدون شمس مباشرة; ground 20°C, عمق الدفن 0.7 م; المقاومة الحرارية للتربة 1.0 K·m/W الرطب و 2.5 كم·م/وات جاف; no additional heat sources. Reference maximum conductor temperature: 90درجة مئوية.

Two Barriers, Two Different Moisture Paths

Swellable components restrict water movement along the screen region after moisture enters. Conductor water blocking is a separate construction feature, and damaged sheaths require repair.

A metal/polymer laminate beneath the PE sheath forms the radial moisture barrier. Its continuity and bond to the sheath support that function; the longitudinal blocking components address water travel along the screened core.

Joints, terminations and cable ends complete the moisture-protection system. Accessory installation includes the specified barrier preparation and sealing method.

Functional diagram comparing water movement along a cable with radial moisture ingress through its wall
Longitudinal water blocking and the radial laminate address different moisture paths. Functional schematic only.

N2XS2Y, N2XS(ف)2Y and N2XS(فلوريدا)2ي

بناءMoisture-control distinction
كابل N2XS2YCopper/XLPE/PE construction; the name does not specify the FL laminated radial barrier.
N2XS(ف)2والكابلAdds longitudinal water blocking, without the FL radial laminate.
N2XS(فلوريدا)2والكابلCombines longitudinal blocking with a laminated radial moisture barrier beneath PE.

Adding longitudinal blocking or a radial laminate changes the cable build and accessory preparation. Tape arrangement and barrier details follow the construction drawing.

Screen Size and Accessory Fit

In 1×240/25, the copper phase conductor is 240 mm² and the metallic screen 25 مم². منطقة الشاشة, fault duration and bonding determine the screen fault-current duty.

Insulation diameter determines the stress-control interface; overall cable diameter determines entry seals. The selected 240/25 reference has an approximate overall diameter of 40 mm and mass of 3.303 كجم/م.

Three separate single-core cables form a three-phase circuit. Their physical arrangement and screen bonding influence losses and rating. The table uses solidly bonded screens in touching trefoil; a different layout needs its own calculation. MV screen-bonding arrangements are explained in the supporting technical article.

Diagram identifying a 240 mm2 phase conductor and 25 mm2 metallic screen, with three separately sheathed single-core cables
The conductor and metallic screen have separate cross-sectional areas; three single-core cables form a three-phase circuit. Not to scale.

Fixed Distribution and Installation Limits

The model is used for fixed network connections, industrial feeders and substation circuits where a screened copper cable with both moisture-control features is specified. Underground and duct routes also depend on soil conditions, الصرف, mechanical protection and the installation design.

This unarmoured construction uses route-appropriate mechanical protection. Indoor routes with flame, smoke or gas requirements need the corresponding sheath system and fire-performance tests.

The test schedule addresses conductor resistance, العزل, التفريغ الجزئي, oversheath integrity and longitudinal water penetration. ال نطاق النشر الرسمي describes the fixed-distribution cable framework.

N2XS(فلوريدا)2Y Questions

Does FL mean the copper conductor is water blocked?

The reference construction has longitudinal blocking in the screen region and a radial laminate under the sheath. Water blocking within the copper conductor is specified separately.

Can N2XS(فلوريدا)2Y replace N2XS(ف)2Y without changing the accessories?

The radial barrier changes the cable build and its preparation at the accessory. Compatibility follows the actual insulation diameter, ترتيب الشاشة, sheath dimensions and barrier-sealing method.

Is the aluminium laminate an armour layer?

The laminate is a radial moisture barrier beneath the PE sheath. Mechanical armour is a separate layer used where the route requires integral impact protection.

Does water blocking make this a submarine cable?

This model is designed for fixed distribution routes. Submarine service requires a cable system designed for marine pressure, أحمال التثبيت, armour and accessories.