Calcolatore della portata del cavo

Cable ampacity is the current a cable can carry continuously under specified installation and temperature conditions. The same conductor size can have different current ratings in free air, a conduit or an underground duct. Use this cable ampacity calculator to compare preliminary copper and aluminum cable options, see the effect of thermal conditions and check a proposed load against the estimate.

Start with the actual cable construction and route. The explanation below connects each input to the result, shows a worked 240 mm² example and separates a preliminary estimate from a project-specific cable rating.

Estimate the current carrying capacity of copper or aluminum power cables under different insulation, installazione, temperatura, raggruppamento e condizioni del suolo.

Cable Parameters

Installation Conditions

Air temperature around the installed cable.
Use the number of loaded circuits installed together.
2.5 K·m/W is used as a neutral reference value.
The calculator adjusts a reference ampacity using material, isolamento, costruzione del cavo, installazione, temperatura, grouping and soil-condition correction factors.

Optional Load Check

Enter 0 if you only want the estimated cable ampacity.

Risultati del calcolo

Estimated Ampacity per Run —
Total Available Ampacity —
Recommended Design Current —
ca. Power Capacity —

Applied Correction Factors

Materiale —
Isolamento —
Costruzione —
Installazione —
Temperatura —
Raggruppamento —
Soil —
Combined Factor —
Selected Cable —
Installazione —
Reference Ampacity —
Adjusted Ampacity per Run —
Parallel Runs —
Actual Load —
Load Utilization —
Avviso tecnico

This tool provides a preliminary current-carrying-capacity estimate. Final cable ampacity must be verified using the applicable project standard and the actual cable construction, installation arrangement, ambiente termico, bonding system, armour or metallic sheath losses, soil conditions and other relevant engineering parameters.

Large MV and HV cables, heavily grouped circuits and critical underground installations should be evaluated using a complete thermal calculation based on actual project data.

Need an exact cable selection?

Send XWA the voltage class, dimensione del conduttore, corrente di carico, metodo di installazione, lunghezza del percorso, ambient or soil conditions and required standard for a project-specific cable recommendation.

Choose inputs that describe the installed cable

A useful ampacity estimate starts with the route, rather than the load alone. Compare options by changing one condition at a time, keeping the other inputs consistent.

IngressoCosa inserirePerché è importante
Materiale e dimensioniRame o alluminio; nominal conductor area in mm².Material and cross-section affect electrical resistance and heating. For AWG or kcmil, use the conductor-size conversion guide first.
IsolamentoThe selected PVC, XLPE or EPR option.The model assumes 70°C for PVC and 90°C for XLPE/EPR. Use the actual cable’s declared temperature rating for final selection.
Costruzione di caviSingle-core or the available multicore arrangement.The tool applies a construction factor. Actual loaded-core count, neutral loading and phase formation require a separate design check.
InstallazioneFree air, tray/open support, conduit in air, direct buried or underground duct.Each route dissipates heat differently.
TemperaturaSurrounding air temperature, or soil temperature at cable depth for buried options.This is the surrounding temperature, not the conductor’s maximum operating temperature.
RaggruppamentoNumber of loaded circuits installed together.Adjacent circuits add heat. The tool groups nine or more circuits under its “9+” option.
Corse paralleleNumber of parallel paths per phase.The tool multiplies per-run capacity by this number. Equal current sharing and mutual heating still need verification.
Resistività termica del suoloFor buried options, use the project value in K·m/W where available.Higher resistivity means poorer heat transfer. The tool’s 2.5 K·m/W reference is a calculation assumption, not a site measurement.
Optional load and systemTotal circuit current, AC/DC system, voltage and AC power factor. Enter zero load for capacity-only estimation.Load is compared with total estimated capacity. System voltage and power factor affect the displayed power estimate, not the thermal ampacity.

Read ampacity, design current and load utilization separately

Estimated ampacity per run is the reference current after the selected factors are applied. Total available ampacity multiplies that estimate by the number of parallel runs. Both are preliminary thermal estimates.

Recommended design current È 90% of the total estimate in this tool. That 10% margin is a calculator convention, not a universal IEC or NEC requirement. The displayed PASS or ENGINEERING CHECK compares the entered load against these model thresholds; it does not confirm protective-device coordination or installation compliance.

Load utilization is load current divided by total estimated ampacity. Approximate power capacity uses the tool’s 90% design-current value, system voltage and power factor. For three-phase AC, inserire la tensione concatenata; for single-phase AC or DC, enter the voltage across the load.

How this ampacity calculator estimates current capacity

The tool starts with an internal reference-current table and multiplies it by simplified adjustment factors. The factor display makes the effect of each selected condition visible:

IOrun = Iriferimento × kmateriale × kisolamento × kcostruzione × kinstallazione × ktemperatura × kraggruppamento × ksuolo

Total estimated current = Irun × parallel runs. The model uses 30°C air or 20°C soil as its temperature reference, depending on the installation selected. Its displayed factors are rounded; the calculation uses their underlying values.

The internal reference table and generic multipliers are the basis of this estimator, rather than a published ampacity table for every selectable cable. Treat them as a consistent comparison model. A complete thermal calculation uses actual dimensions, electrical losses, thermal resistances and installation geometry; that is a different level of analysis.

For the power display: three-phase AC uses P = √3 × V × Iprogetto × power factor; single-phase AC uses P = V × Iprogetto × power factor; DC uses P = V × Iprogetto. Divide watts by 1,000 for kW. Motor output would additionally depend on efficiency.

Esempio lavorato: 240 mm² copper cable on a tray

Seleziona il rame, 240 mm², XLPE, single-core, tray/open support, 30°C air, one loaded circuit and one run per phase. For the optional check, use a 400 A load on a 400 V three-phase system at 0.90 fattore di potenza.

Fare un passoCalculation in this toolDisplayed result
Reference currentInternal 240 riferimento mm²546 UN
Combined correction1 × 1 × 1 × 0.95 × 1 × 1 × 10.950
Per run / total546 × 0.95; one parallel run519 UN
Tool’s design current518.7 × 0.90467 UN
Load utilization400 ÷ 518.7 × 10077.1%
Approximate power√3× 400 × 466.83 × 0.90 ÷ 1,000291 kW

Now change only grouping to two circuits. The model applies 0.85, reducing estimated capacity to 441 A and its design-current value to 397 UN. The same 400 A load moves into ENGINEERING CHECK. This illustrates why route conditions can change the assessment even when conductor size stays the same. These numbers reproduce this calculator, not a universal 240 mm² cable rating.

Why installation conditions change cable ampacity

Heat must leave the cable

Current produces losses within the conductor. Isolamento, sheaths and the surroundings form the heat-transfer path. A higher surrounding temperature leaves less temperature difference for cooling, while enclosed routes and neighbouring loaded circuits can limit heat removal.

Underground routes need soil data

Soil temperature and thermal resistivity are separate inputs. Moisture conditions, backfill and possible drying also influence the thermal environment. Burial depth and duct-bank geometry are important to a detailed calculation, even though this estimator has no fields for them.

Parallel cables need a physical arrangement

Doubling runs doubles the arithmetic capacity in this tool. In an installation, conductor matching, terminazione, disposizione delle fasi, spacing and shared heating determine how effectively those runs work together. Set grouping to represent the loaded-circuit arrangement; parallel count does not automatically resolve that grouping question.

Our approach is to identify the most thermally demanding route section before finalising the cable schedule. A short duct or enclosed section can deserve more attention than a much longer, well-ventilated part of the route.

Standards and the final current-rating check

CEI 60287-1-1 fornisce equazioni di valutazione della corrente in stato stazionario e calcoli delle perdite. CEI 60364-5-52 addresses selection and erection of low-voltage wiring systems; use the project-adopted edition and amendments. These references explain the engineering context, rather than certifying this estimator as a full implementation of either standard.

For MV/HV circuits, large conductors and critical underground feeders, use the actual cable design, conductor AC losses, screen/sheath or armour losses, bonding arrangement and route thermal data. The same principle applies below any particular conductor-size threshold: the project duty determines the level of analysis required.

Use the result as one part of cable selection

  1. Confirm the load and thermal duty. Record the installed arrangement, ambient/soil conditions and grouping with the current estimate.
  2. Check voltage drop. Usa il cable voltage-drop calculator for a separate route-length check.
  3. Check the circuit protection. Coordinate overload and short-circuit protection, fault withstand and terminal temperature limits.
  4. Match the product construction. Relate the result to the actual low-voltage cable O medium-voltage cable specification rather than conductor area alone.

Cable ampacity questions

What is the ampacity of a 95, 120 O 240 cavo mm²?

There is no single current rating for a conductor area. Select the material, isolamento, construction and installation conditions to obtain a preliminary estimate, then verify it against the actual cable and route.

Is cable ampacity the same as load current?

Ampacity describes capacity under specified conditions. Load current describes the demand placed on the circuit. The calculator compares demand with its estimated capacity.

Does a higher system voltage increase ampacity?

Changing the voltage field changes the displayed power estimate, not the model’s thermal current capacity. The cable still needs the correct voltage class for the circuit.

Can this result be used as an NEC ampacity-table value?

The tool uses its own reference values and adjustment model. For an NEC project, select the applicable table and correction requirements, including installation and terminal-temperature conditions.

Why do XLPE and EPR give the same result here?

The tool assigns both options a 90°C temperature assumption. Actual cable ratings can differ with construction and compound properties, which need to be included in the project specification.

Discuss a project cable requirement with XWA

Send the voltage class, corrente di carico, conductor preference, lunghezza del percorso, installation arrangement, circuit grouping and available soil or ambient data. A cable schedule or route drawing helps turn a preliminary estimate into a focused product and quotation discussion. E-mail: info@xwacable.com.