Cavo N2XSEY is a three-core medium-voltage power cable with stranded copper conductors, screened XLPE insulation and a common PVC outer sheath. Three phase cores form one assembled cable for fixed distribution.
The reference CU/XLPE/CTS/PVC construction uses metallic screening but no armour. The shared sheath distinguishes it from a circuit of three separate single-core cables and changes handling mass, cable-entry dimensions and installation geometry.

COSTRUZIONE
- Conduttori
- Three stranded copper phase conductors
- Insulated cores
- Semiconductive screens and XLPE insulation
- Schermi metallici
- Copper tape screening in the reference construction
- Assembly
- Filler and common PVC sheath; non armato
CARATTERISTICHE
- Tensione di riferimento
- 12/20 kV for the displayed dataset
- Core layout
- Three screened cores in one cable body
- Riferimento termico
- 90°C temperatura massima operativa del conduttore nel progetto della sorgente
- Contesto standard
- CEI 60502-2 and relevant VDE/HD project requirements
N2XSEY for Fixed Power Distribution
Voltaggio, le dimensioni del conduttore/schermo e le condizioni del percorso definiscono la configurazione del progetto.
N2XSEY Cable Technical Data
Dati di riferimento consigliati: valori pubblicati per un confronto preliminare. Dimensioni finali della fornitura, le valutazioni e la gamma di dimensioni seguono la scheda tecnica XWA concordata.
| Dimensioni del cavo (mm²) | Resistenza CC 20°C (Ω/km) | ca. DI (mm) | ca. massa (kg/km) | Aria (UN) | Terra (UN) |
|---|---|---|---|---|---|
| 3 X 95/16 | 0.1930 | 67.0 | 6900 | 326 | 316 |
| 3 X 150/25 | 0.1240 | 74.5 | 9250 | 426 | 404 |
| 3 X 185/25 | 0.0991 | 78.5 | 10650 | 488 | 457 |
| 3 X 240/25 | 0.0754 | 85.0 | 13000 | 576 | 532 |
| 3 X 300/25 | 0.0601 | 90.0 | 15250 | 654 | 599 |
| 3 X 400/35 | 0.0470 | 98.0 | 19100 | 750 | 685 |
Three-core CU/XLPE/CTS/PVC, 12/20 kV. Diameter and mass refer to the assembled cable; the slash notation identifies the separately specified metallic-screen section.
Ampiezza di riferimento: one system; aria 30°C, fattore di carico 1.0; terra 20°C, profondità 0.7 M, resistività termica 1.0 K·m/W, fattore di carico 0.7. Limite del conduttore di riferimento: 90°C. Continuous full-load burial requires a rating calculated at load factor 1.0.
Three-core construction and accessory interfaces
N2XSEY assembles the three phase cores within a common sheath. Separate single-core cables permit flat or trefoil formation; each arrangement has its own current-rating, handling and support requirements.
Termination stress-control components fit the insulation diameter and screen treatment. Glands and entry seals fit the complete cable diameter. The 3×240/25 reference is approximately 85 mm in diameter and 13 kg/m, before drum tare; handling calculations therefore use assembly mass, not copper mass alone.
Applicazioni e condizioni di installazione
Distribuzione industriale, substation connections and suitable underground or ducted feeders can use this combined three-core assembly. Diametro del cavo, mass and bending limits inform route access and pulling equipment. Routes requiring armour, water blocking or enhanced fire performance use the corresponding construction.
The manufacturing specification defines screens, insulation and sheath thicknesses, accessory dimensions and tests for the three-core assembly. The official standard scope descrive la struttura dei cavi di distribuzione fissa.
N2XSEY and Related Constructions
| Modello | Differenza principale |
|---|---|
| N2XSY single-core cable | Each phase cable has its own sheath; circuit geometry and bonding need separate assessment. |
| 20 Gamma di cavi kV | Voltage-class context for 12/20(24) kV projects, rather than an exact three-core model. |
| Armoured MV construction | Mechanical armour adds a separate layer and changes the specified design and dimensions. |
N2XSEY Cable FAQs
Does N2XSEY mean the cable is armoured?
The reference N2XSEY construction is screened and unarmoured. Its metallic screen performs an electrical duty; mechanically protected variants add a separate armour layer.
Can 12/20 kV dimensions be used for a 6/10 kV variant?
The table covers the stated 12/20 costruzione kV. UN 6/10 kV version uses its own insulation dimensions and construction-specific rating data.
Is N2XSEY the same as three N2XSY cables?
N2XSEY combines three phase cores inside a common sheath. Three N2XSY cables are separately sheathed single-core products, with different handling and installation arrangements.
Imparentato: Cavo di media tensione · Tipi e modelli di cavi