N2XSEY Kablosu

N2XSEY cable is a three-core medium-voltage power cable with stranded copper conductors, screened XLPE insulation and a common PVC outer sheath. Three phase cores form one assembled cable for fixed distribution.

The reference CU/XLPE/CTS/PVC construction uses metallic screening but no armour. The shared sheath distinguishes it from a circuit of three separate single-core cables and changes handling mass, cable-entry dimensions and installation geometry.

Concept illustration of three individually screened copper cores within a common PVC cable sheath
Three screened copper cores inside one PVC sheath. Concept illustration, ölçekli değil.

YAPI

İletkenler
Three stranded copper phase conductors
Insulated cores
Semiconductive screens and XLPE insulation
Metallic screens
Copper tape screening in the reference construction
Assembly
Filler and common PVC sheath; zırhsız

ÖZELLİKLER

Referans voltajı
12/20 kV for the displayed dataset
Core layout
Three screened cores in one cable body
Termal referans
90°C kaynak tasarımında maksimum çalışma iletken sıcaklığı
Standart bağlam
IEC 60502-2 and relevant VDE/HD project requirements

N2XSEY for Fixed Power Distribution

Gerilim, iletken/ekran boyutu ve güzergah koşulları proje konfigürasyonunu tanımlar.

Fiyat teklifi isteyin

N2XSEY Cable Technical Data

Önerilen referans verileri. Nihai boyutlar ve derecelendirmeler, onaylanmış proje konfigürasyonuna uygundur; seçilen satırlar onaylanmış bir XWA üretim aralığı değil.

Kablo boyutu
(mm²)
DC direnci
20°C (Ω/km)
Yaklaşık. İLE İLGİLİ
(mm)
Yaklaşık. yığın
(kg/km)
Hava
(A)
Zemin
(A)
3 X 95/160.193067.06900326316
3 X 150/250.124074.59250426404
3 X 185/250.099178.510650488457
3 X 240/250.075485.013000576532
3 X 300/250.060190.015250654599
3 X 400/350.047098.019100750685

Three-core CU/XLPE/CTS/PVC, 12/20 kV. Mass and diameter describe the assembled cable. The /screen notation does not create a fourth phase core; the approved drawing defines the screen arrangement.

Referans hacmi: one system; hava 30°C, yük faktörü 1.0; toprak 20°C, derinlik 0.7 M, termal direnç 1.0 K·m/W, yük faktörü 0.7. Referans iletken sınırı: 90°C. The buried ratings do not represent a continuously fully loaded circuit at load factor 1.0.

Three-core construction and accessory interfaces

A single overall sheath fixes the relative positions of the three phase cores. Three separate single-core cables permit a chosen flat or trefoil arrangement. Equal voltage and conductor area do not make their current-rating or handling data interchangeable.

Termination stress-control components fit the insulation diameter and screen treatment. Glands and entry seals fit the complete cable diameter. The 3×240/25 reference is approximately 85 mm in diameter and 13 kg/m, before drum tare; handling calculations therefore use assembly mass, not copper mass alone.

Schematic of three individually screened copper cores, XLPE izolasyonu, filler and common PVC sheath
Three screened cores share one outer sheath; the drawing is explanatory and not to scale.
Diagram separating cable voltage designation from insulation diameter and overall diameter for accessory fit
Voltage class alone does not establish termination, joint or gland compatibility.

Uygulamalar ve Kurulum Koşulları

Endüstriyel dağıtım, substation connections and underground or ducted feeder sections can suit a combined three-core assembly. Pulling equipment, route access and bending limits must fit the complete cable. Zırh, water blocking and enhanced fire-performance sheaths require separately identified constructions rather than assumptions about the N2XSEY name.

The production definition must identify screen arrangement, insulation and sheath thicknesses, accessory diameters and applicable tests for the assembled three-core cable. The official standard scope concerns fixed distribution installations, not an automatic claim of approval for special service.

N2XSEY and Related Constructions

ModeliAna fark
N2XSY single-core cableEach phase cable has its own sheath; circuit geometry and bonding need separate assessment.
20 kV kablo aralığıVoltage-class context for 12/20(24) kV projects, rather than an exact three-core model.
Armoured MV constructionMechanical armour adds a separate layer and changes the specified design and dimensions.

N2XSEY Cable FAQs

Does N2XSEY mean the cable is armoured?

HAYIR. The reference screened construction is unarmoured. A metallic screen provides an electrical function and is not mechanical armour.

Can 12/20 kV dimensions be used for a 6/10 kV variant?

HAYIR. The values here belong only to the stated 12/20 kV inşaat. A different voltage design needs its own dimensional and rating data.

Is N2XSEY the same as three N2XSY cables?

HAYIR. N2XSEY combines three phase cores within one sheath. Separate N2XSY cables have different assembly, handling and installation arrangements.