N2XSEY cable is a three-core medium-voltage power cable with stranded copper conductors, screened XLPE insulation and a common PVC outer sheath. Three phase cores form one assembled cable for fixed distribution.
The reference CU/XLPE/CTS/PVC construction uses metallic screening but no armour. The shared sheath distinguishes it from a circuit of three separate single-core cables and changes handling mass, cable-entry dimensions and installation geometry.

YAPI
- İletkenler
- Three stranded copper phase conductors
- Insulated cores
- Semiconductive screens and XLPE insulation
- Metallic screens
- Copper tape screening in the reference construction
- Assembly
- Filler and common PVC sheath; zırhsız
ÖZELLİKLER
- Referans voltajı
- 12/20 kV for the displayed dataset
- Core layout
- Three screened cores in one cable body
- Termal referans
- 90°C kaynak tasarımında maksimum çalışma iletken sıcaklığı
- Standart bağlam
- IEC 60502-2 and relevant VDE/HD project requirements
N2XSEY for Fixed Power Distribution
Gerilim, iletken/ekran boyutu ve güzergah koşulları proje konfigürasyonunu tanımlar.
N2XSEY Cable Technical Data
Önerilen referans verileri. Nihai boyutlar ve derecelendirmeler, onaylanmış proje konfigürasyonuna uygundur; seçilen satırlar onaylanmış bir XWA üretim aralığı değil.
| Kablo boyutu (mm²) | DC direnci 20°C (Ω/km) | Yaklaşık. İLE İLGİLİ (mm) | Yaklaşık. yığın (kg/km) | Hava (A) | Zemin (A) |
|---|---|---|---|---|---|
| 3 X 95/16 | 0.1930 | 67.0 | 6900 | 326 | 316 |
| 3 X 150/25 | 0.1240 | 74.5 | 9250 | 426 | 404 |
| 3 X 185/25 | 0.0991 | 78.5 | 10650 | 488 | 457 |
| 3 X 240/25 | 0.0754 | 85.0 | 13000 | 576 | 532 |
| 3 X 300/25 | 0.0601 | 90.0 | 15250 | 654 | 599 |
| 3 X 400/35 | 0.0470 | 98.0 | 19100 | 750 | 685 |
Three-core CU/XLPE/CTS/PVC, 12/20 kV. Mass and diameter describe the assembled cable. The /screen notation does not create a fourth phase core; the approved drawing defines the screen arrangement.
Referans hacmi: one system; hava 30°C, yük faktörü 1.0; toprak 20°C, derinlik 0.7 M, termal direnç 1.0 K·m/W, yük faktörü 0.7. Referans iletken sınırı: 90°C. The buried ratings do not represent a continuously fully loaded circuit at load factor 1.0.
Three-core construction and accessory interfaces
A single overall sheath fixes the relative positions of the three phase cores. Three separate single-core cables permit a chosen flat or trefoil arrangement. Equal voltage and conductor area do not make their current-rating or handling data interchangeable.
Termination stress-control components fit the insulation diameter and screen treatment. Glands and entry seals fit the complete cable diameter. The 3×240/25 reference is approximately 85 mm in diameter and 13 kg/m, before drum tare; handling calculations therefore use assembly mass, not copper mass alone.
Uygulamalar ve Kurulum Koşulları
Endüstriyel dağıtım, substation connections and underground or ducted feeder sections can suit a combined three-core assembly. Pulling equipment, route access and bending limits must fit the complete cable. Zırh, water blocking and enhanced fire-performance sheaths require separately identified constructions rather than assumptions about the N2XSEY name.
The production definition must identify screen arrangement, insulation and sheath thicknesses, accessory diameters and applicable tests for the assembled three-core cable. The official standard scope concerns fixed distribution installations, not an automatic claim of approval for special service.
N2XSEY and Related Constructions
| Modeli | Ana fark |
|---|---|
| N2XSY single-core cable | Each phase cable has its own sheath; circuit geometry and bonding need separate assessment. |
| 20 kV kablo aralığı | Voltage-class context for 12/20(24) kV projects, rather than an exact three-core model. |
| Armoured MV construction | Mechanical armour adds a separate layer and changes the specified design and dimensions. |
N2XSEY Cable FAQs
Does N2XSEY mean the cable is armoured?
HAYIR. The reference screened construction is unarmoured. A metallic screen provides an electrical function and is not mechanical armour.
Can 12/20 kV dimensions be used for a 6/10 kV variant?
HAYIR. The values here belong only to the stated 12/20 kV inşaat. A different voltage design needs its own dimensional and rating data.
Is N2XSEY the same as three N2XSY cables?
HAYIR. N2XSEY combines three phase cores within one sheath. Separate N2XSY cables have different assembly, handling and installation arrangements.
İlgili: Orta Gerilim Kablosu · Kablo Çeşitleri ve Modelleri