15kV Cable for 8.7/15(17.5)kV Distribution Projects
15kV Kablo from XWA uses an 8.7/15(17.5)kV XLPE screened construction for transformer substations, endüstriyel besleyiciler, renewable energy collection systems and underground distribution networks.
XWA 15kV Cable
15kV Kablo corresponds to the IEC voltage class formally written as U0/sen(Bir) = 8.7/15(17.5)kV. In some markets the same voltage class appears in 13.8kV and 15kV distribution systems.
XWA supplies this XLPE screened medium voltage cable with copper or aluminum conductors, tek çekirdekli veya üç çekirdekli yapı, copper tape or copper wire screen, optional armor and PVC, PE or LSZH sheath materials according to the project specification.

Gerilim Sınıfı
8.7/15(17.5)kV for 13.8 kV ve 15 kV medium voltage distribution systems under IEC-oriented specifications.
Construction Range
Single-core and three-core cable with copper or aluminum conductor, screened XLPE insulation and route-specific sheath or armor.
Project Use
Transformer substations, endüstriyel besleyiciler, municipal distribution, renewable energy collection and underground cable routes.
15kV XLPE Cable Construction
A typical 8.7/15(17.5)kV medium voltage cable includes a compacted conductor, iletken ekran, XLPE izolasyonu, yalıtım ekranı, metalik ekran, bedding or separator layer, optional armor and outer sheath. XWA matches the final layer design to the core construction and installation route.
| Katman | Common Construction |
|---|---|
| İletken | Bakır veya alüminyum, Sınıf 2 stranded compacted conductor |
| Insulation system | İletken ekranı, XLPE insulation and insulation screen |
| Metalik ekran | Copper tape screen or copper wire screen with continuity design |
| Armor option | SWA, STA or AWA according to core type and project route |
| Dış kılıf | PVC, PE, MDPE, HDPE or LSZH where specified |

Technical Data for 15kV Cable
The data below is Önerilen Referans Verileri for common 8.7/15(17.5)kV XLPE screened MV cable constructions under IEC 60502-2. XWA confirms final manufacturing data through the approved cable schedule, installation conditions and project specification.
Single-Core 15kV Cable Reference Data
| Size | DC resistance 20C (ohm/km) | Yalıtım (mm) | Yaklaşık. OD (mm) | Yaklaşık. ağırlık (kg/km) | Ampacity air 30C (A) | Ampacity ground 20C (A) |
|---|---|---|---|---|---|---|
| 1 X 35/16 | 0.524 | 4.5 | 26 | 920 | 198 | 188 |
| 1 X 50/16 | 0.387 | 4.5 | 27 | 1100 | 237 | 221 |
| 1 X 70/16 | 0.268 | 4.5 | 29 | 1300 | 295 | 270 |
| 1 X 95/16 | 0.193 | 4.5 | 30 | 1580 | 359 | 322 |
| 1 X 120/16 | 0.153 | 4.5 | 32 | 1830 | 414 | 365 |
| 1 X 150/25 | 0.124 | 4.5 | 33 | 2160 | 471 | 410 |
| 1 X 185/25 | 0.0991 | 4.5 | 35 | 2520 | 537 | 459 |
| 1 X 240/25 | 0.0754 | 4.5 | 38 | 3100 | 633 | 530 |
| 1 X 400/35 | 0.0470 | 4.5 | 43 | 4650 | 828 | 668 |
Three-Core 15kV Cable Reference Data
| Size | DC resistance 20C (ohm/km) | Yalıtım (mm) | Yaklaşık. OD (mm) | Yaklaşık. ağırlık (kg/km) | Ampacity air 30C (A) | Ampacity ground 20C (A) |
|---|---|---|---|---|---|---|
| 3 X 35 | 0.524 | 4.5 | 52-58 | 2350-3000 | 138-165 | 148-175 |
| 3 X 50 | 0.387 | 4.5 | 56-64 | 3000-3800 | 165-195 | 175-205 |
| 3 X 70 | 0.268 | 4.5 | 62-70 | 4000-5000 | 200-238 | 210-252 |
| 3 X 95 | 0.193 | 4.5 | 68-78 | 5200-6400 | 242-290 | 252-305 |
| 3 X 120 | 0.153 | 4.5 | 74-84 | 6300-7800 | 278-330 | 288-345 |
| 3 X 150 | 0.124 | 4.5 | 80-92 | 7700-9300 | 315-375 | 325-390 |
| 3 X 185 | 0.0991 | 4.5 | 88-100 | 9300-11200 | 360-430 | 370-445 |
| 3 X 240 | 0.0754 | 4.5 | 100-114 | 11800-14300 | 420-505 | 430-520 |

Applications and Route Conditions
XWA manufactures this voltage class for medium voltage distribution feeders, transformer substations, industrial power intake, wind and solar collection circuits, mining distribution routes, municipal underground networks and duct or tray installations.
Larger conductor sizes, thermal spacing and bonding design often point to single-core cable. Compact routes, shorter runs, indoor substations and installations that need combined cable handling often use three-core cable.
Underground or wet-route conditions can require PE sheath and water-blocking options. Projects that include smoke and halogen performance requirements can specify LSZH sheath.
Related MV Cable Pages
SSS
What is 15kV Cable?
15kV Cable is a medium voltage power cable with rated voltage U0/U(Bir) of 8.7/15(17.5)kV. Distribution systems, transformer substations, industrial feeders and renewable energy collection routes use this voltage class.
Is 8.7/15kV the same as 15kV Cable?
In IEC-based specifications, 8.7/15(17.5)kV is the formal voltage designation behind the common market name. Some projects also use 13.8kV Cable as the market name for this voltage class.
Which standard applies to 8.7/15kV Medium Voltage Cable?
IEC 60502-2 normally covers extruded-insulation medium voltage power cables in this voltage range. Project specifications can also include local utility requirements, national standards or additional test documentation.
Can this cable be single-core or three-core?
Evet. XWA supplies this voltage class in single-core and three-core constructions. Utility feeders and larger conductor sizes often use single-core cable, while compact route layouts often use three-core cable.
What conductor sizes are common for this voltage class?
Common copper or aluminum conductor sizes include 35mm2 to 400mm2 for many project schedules, with larger sizes possible depending on construction, current rating and installation conditions.
Can this cable be armoured?
Evet. Route designs can include steel wire armor, steel tape armor or aluminum wire armor where mechanical protection matters. Armor selection depends on single-core or three-core construction, fault-current design and installation route.
How does XWA prepare cable data for this voltage class?
XWA prepares the cable construction, dimensional data, current-rating discussion, drum schedule and test documentation according to the confirmed voltage class, iletken malzeme, çekirdek sayısı, screen design, zırh, sheath and installation route.
Contact XWA for 15kV Cable
XWA prepares project offers around voltage class, iletken malzeme, core construction, ekran tipi, zırh, sheath design, drum length and required standard.
Gerilim: 8.7/15(17.5)kV Common names: 13.8kV Kablo / 15kV Kablo Standart: IEC 60502-2 proje özellikleri