N2XSH Cable

N2XSH cable is a screened copper power cable with XLPE insulation and a low-smoke, halogen-free outer sheath. The medium-voltage single-core design described here serves fixed power circuits where cable fire behaviour is an important part of the route specification.

Its defining difference from PVC- or PE-sheathed MV alternatives is the outer-sheath system, not a change from XLPE insulation. Electrical rating, mechanical protection and reaction-to-fire classification remain separate requirements. Low-smoke halogen-free construction does not by itself establish operation during a fire.

N2XSH single-core cable cutaway and cross-section with a stranded copper conductor and copper wire screen
N2XSH construction illustration with copper conductor, screened insulation and outer sheath; not to scale.

CONSTRUÇÃO

Phase conductor
Stranded copper, aula 2
Sistema de isolamento
XLPE between inner and outer semiconductive layers
Tela metálica
Copper wires; associated tape arrangement follows the declared design
Outer protection
Low-smoke, halogen-free sheath; unarmoured reference

CARACTERÍSTICAS

MV designations
6/10, 12/20 e 18/30 kV; voltage-specific constructions
Reference table
Núcleo único 12/20 (24) kV, 95 para 500 mm² selected sizes
Instalação
Fixed distribution, building supply and industrial cable routes
Performance basis
Electrical, fumaça, gas and flame tests assessed separately

N2XSH Project Enquiries

Discuss the voltage, conductor section, screen duty and fire-performance requirements with XWA.

Solicite um orçamento

Baixa fumaça, Halogen-Free and Flame Behaviour

A cable route through an occupied building or an enclosed service area can have different fire requirements from an external feeder. N2XSH addresses the sheath side of that specification while retaining the screened XLPE construction of an MV circuit. Its suitability depends on the complete declared design, not the abbreviation alone.

PropertyWhat it establishesO que não estabelece
Smoke emissionSmoke behaviour under the specified cable-burning test, como IEC 61034-2.No smoke under every possible fire condition.
Combustion gasesHalogen acid-gas assessment and acidity/conductivity assessment under the applicable IEC 60754 peças.A universal absence of hazardous combustion products.
Propagação de chamaPerformance in the specified single-cable or bunched-cable test.Continued circuit operation while exposed to fire.
Declared fire classAn assessed reaction-to-fire classification for the documented product.A class automatically assigned to every cable called N2XSH.

O oficial smoke-density test scope concerns smoke measurement under defined burning conditions. That evidence cannot substitute for an electrical circuit-integrity test. Emergency circuits with a specified survival time require the appropriate cable system and separate evidence.

N2XSH 12/20 kV Reference Dimensions

Dados de referência recomendados. The table describes one published single-core copper construction with a copper wire screen. These dimensions and masses are not XWA guaranteed values or a confirmed supply range. Final cable data follows the approved manufacturing specification.

Conductor/screen
(mm²)
Isolamento
(milímetros)
Over insulation
(milímetros)
Minimum sheath
(milímetros)
Aprox.. DE
(milímetros)
Aprox.. massa
(kg/km)
1 x 95/165.524.02.136.01965
1 x 120/165.526.02.138.02235
1 x 150/255.527.02.139.02630
1 x 185/255.529.02.141.03035
1 x 240/255.531.02.143.03600
1 x 300/255.533.02.146.04220
1 x 400/355.536.02.149.05230
1 x 500/355.540.02.152.06290

Each row is for 12/20 kV, maximum system voltage 24 kV. The screen section follows the slash; 1×240/25 has one 240 mm² phase conductor and a separate 25 mm² screen. Values from 6/10 ou 18/30 kV designs are not interchangeable with this table.

No universal ampacity is assigned here. The current rating depends on circuit arrangement, colagem de tela, surrounding temperature, soil or duct conditions and neighbouring heat sources. A project calculation and the approved cable construction are required; conductor area or sheath designation alone is insufficient.

The Two Diameters That Matter at a Termination

An MV termination interfaces with several surfaces, not just a nominal conductor size. The diameter over insulation sets one accessory interface; the complete cable diameter sets another at the outer entry or seal. A termination range and a cable gland range therefore refer to different dimensions.

In the selected 240/25 reference, the insulation diameter is 31 mm while the complete cable diameter is approximately 43 milímetros. Usando 43 mm to select an insulation interface confuses those surfaces. Manufacturing tolerances and the accessory’s own specified limits remain part of the fit assessment.

The semiconductive insulation screen also has its own preparation method. Strippable and bonded screen designs require the appropriate preparation procedure and tools. A cutaway illustration does not establish which removal method applies to the supplied cable.

Building Entry, Cable Trays and Protected Routes

Screened LSZH MV cables are relevant to industrial power distribution, substations and building feeders where the installation specification calls for controlled smoke and gas behaviour. A tunnel application requires the actual fire classification, route arrangement and local acceptance criteria; the word LSZH alone is not a tunnel approval.

An exterior-to-interior run can avoid an unnecessary sheath transition only when the same declared cable is suitable on both portions of the route. Exposição UV, standing water, soil contact and fire requirements must all be covered. Some published N2XSH designs restrict outdoor or underground use to protected installation, so direct burial is not a model-wide promise.

The copper screen is not impact armour. Dutos, capas, bandejas, supports or another protection system may be necessary where the route exposes the cable to damage. Water-blocking properties likewise require a specified design; a halogen-free sheath does not provide the longitudinal barriers identified by an (F) variante.

Cable routing remains constrained by the stated installation bend radius, pulling method and support system. The supporting explanation of Raio de curvatura do cabo MT e tensão de tração separates these handling limits from the electrical rating.

N2XSH, N2XSY and N2XS2Y

ModeloOuter-sheath distinctionRelevant specification difference
N2XSHLow-smoke, halogen-free sheathFire-test performance and installation suitability must be defined for the exact construction.
N2XSY cableBainha de PVCPVC and LSZH have different combustion-gas and material characteristics.
N2XS2Y cableBainha PEPE sheath protection does not by itself imply a flame-retardant, low-smoke construction.
N2XS(F)H / N2XS(Flórida)HHalogen-free sheath with additional water barriers(F) identifies longitudinal water blocking; (Flórida) additionally identifies a radial moisture barrier in the specified design.

The comparison concerns copper screened MV constructions. An aluminium-conductor NA2XSH design changes the phase-conductor material as well. Three-core N2XSEH places three screened phase cores inside a common sheath and needs its own dimensional and rating data.

Electrical Tests and Fire Evidence Have Different Jobs

CEI 60502-2 addresses extruded-insulation power cables within its MV scope. alta definição 622 / DIN VDE 0276-622 also appears in established halogen-free MV constructions. The agreed manufacturing standard and voltage designation must identify the actual design; listing several references does not establish simultaneous conformity.

Resistência do condutor, insulation tests, partial-discharge assessment and oversheath tests relate to different electrical or material requirements. The applicable standard determines their method and acceptance limits. Routine production records are not interchangeable with a type-test report, and neither should be inferred from a product illustration.

For fire performance, the report or declaration must identify the assessed construction and the applicable method. A third-party catalogue’s class, certificate or laboratory accreditation cannot be carried over to another manufacturer. The product description here does not claim an XWA CPR class or circuit-survival rating.

N2XSH Cable Questions

Can N2XH replace medium-voltage N2XSH?

Não, not on sheath material alone. The MV construction described here includes electrical screens and voltage-specific insulation. A low-voltage N2XH cable does not become an MV cable because both designs use XLPE and a halogen-free sheath.

Does N2XSH automatically have a B2ca classification?

Não. A reaction-to-fire class belongs to an assessed product construction and its supporting documentation. The N2XSH designation alone does not assign B2ca or any smoke, droplet or acidity subclass.

O que faz 3 x 1 x 240/25 mean for this cable?

It describes three separate single-core cables, each with a 240 mm2 phase conductor and a 25 mm2 metallic screen. It is not one three-core cable under a common sheath. Phase arrangement and screen bonding still need their own design.

Is the copper wire screen mechanical armour?

Não. The metallic screen has electrical screening and specified earth-fault duties. It must not be treated as wire armour against impact or excavation damage. Mechanical protection follows the installation route and declared cable construction.

    Faça um orçamento grátis em 24 Horas

    E-mail*:

    Nome*:

    Seu país:

    Tel*:

    Suas necessidades*: