N2XS(에프)2그리고 케이블 is a screened single-core copper power cable with XLPE insulation, a copper wire screen, longitudinal water-blocking components and a PE outer sheath. It is intended for fixed medium-voltage distribution rather than flexible trailing service.
The copper conductor carries load current; the surrounding screen performs a separate electrical duty. Industrial feeders, substation circuits and underground networks use this construction where the voltage, bonding arrangement and route conditions match the cable-system design.

건설
- 지휘자
- Stranded copper
- 격리
- XLPE between semiconductive conductor and insulation screens
- Screen region
- Copper wires and tape; longitudinal water-blocking components
- 외피
- Black PE; no armour in the reference construction
형질
- Reference voltage
- 12/20 (24) kV
- Core configuration
- 단일 코어; separate conductor and screen areas
- Thermal reference
- 90°C maximum operating conductor temperature in the source design
- Standard context
- HD 620 / DIN VDE 0276-620; agreed project requirements
N2XS(에프)2Y for Fixed Power Distribution
전압, conductor/screen size and route conditions define the project configuration.
N2XS(에프)2Y 케이블 기술 데이터
Recommended reference data. Final dimensions and ratings follow the approved project configuration; the selected rows are not a confirmed XWA production range.
| 케이블 크기 (mm²) | DC 저항 20℃ (Ω/km) | 격리 (mm) | 대략. 의 (mm) | 대략. 대량의 (kg/km) | Air (에이) | Ground (에이) |
|---|---|---|---|---|---|---|
| 1 엑스 95/16 | 0.193 | 5.5 | 32 | 1580 | 361 | 323 |
| 1 엑스 150/25 | 0.124 | 5.5 | 35 | 2212 | 470 | 409 |
| 1 엑스 240/25 | 0.075 | 5.5 | 39 | 3181 | 634 | 532 |
| 1 엑스 300/25 | 0.060 | 5.5 | 42 | 3851 | 724 | 599 |
| 1 엑스 400/35 | 0.047 | 5.5 | 44 | 4795 | 829 | 671 |
| 1 엑스 500/35 | 0.037 | 5.5 | 47 | 5873 | 953 | 754 |
Copper single-core N2XS(에프)2와이, 12/20 kV, copper wire screen and PE sheath. The listed dimensions, mass and current ratings apply to this reference construction and the installation conditions below.
Ampacity basis: one circuit in touching trefoil, screens solidly bonded; air 30°C without direct sun; ground 20°C at 0.7 m depth. Source assumptions include 1.0 K·m/W wet soil and 2.5 K·m/W dry soil, with no additional heat sources. Reference conductor limit: 90℃.
구리 도체, metallic screen and the (에프) 지정
In a reference 1×240/25 건설, 240 mm² belongs to the phase conductor and 25 mm² to the metallic screen. Screen fault-current duty, protection clearing time and accessory connections are separate from continuous conductor ampacity.
그만큼 (에프) construction uses water-blocking components to limit moisture propagation along the cable. N2XS(플로리다)2Y adds a laminated metallic barrier beneath the PE sheath for radial moisture protection. A PE sheath alone does not provide the same barrier construction.
Applications and Installation Conditions
Fixed industrial power intake, substation feeders and underground distribution can use this screened construction. Unarmoured cable still needs route-specific mechanical protection. Indoor fire requirements, water exposure and accessory interfaces must match the stated design; the model name alone does not establish submarine suitability.
The test schedule distinguishes conductor resistance, insulation tests and sheath checks from the evidence for the (에프) 물 장벽. Screen connections and accessory interfaces also belong to the cable-system specification. The IEC publication scope explains the fixed-installation framework; certification requires separate evidence.
N2XS(에프)2Y and Related Constructions
| 모델 | Main difference |
|---|---|
| N2XS2Y cable | 구리 도체, XLPE insulation and PE sheath; longitudinal water blocking is not specified by the N2XS2Y designation. |
| N2XSY cable | Copper screened MV cable with PVC outer sheath. |
| N2XS(플로리다)2와이 | Combines longitudinal water blocking with a laminated metallic barrier beneath the PE sheath for radial moisture protection. |
N2XS(에프)2Y 케이블 FAQ
Are N2XS(에프)2Y and N2XS2Y interchangeable?
자동이 아님. 그만큼 (에프) construction includes longitudinal water blocking; an ordinary PE-sheathed cable should not be assumed to provide the same water-penetration performance.
What does 1×240/25 identify?
One 240 mm² phase conductor and a separately specified 25 mm² metallic screen in the reference construction. The screen is not another power core.
Can the displayed ampacity be used for ducts?
Not directly. The table uses the stated trefoil, bonding and thermal conditions. 덕트, surrounding materials and grouped circuits require the applicable current-rating calculation.