N2XSH Cable

N2XSH cable is a screened copper power cable with XLPE insulation and a low-smoke, halogen-free outer sheath. The medium-voltage single-core design described here serves fixed power circuits where cable fire behaviour is an important part of the route specification.

Its defining difference from PVC- or PE-sheathed MV alternatives is the outer-sheath system, not a change from XLPE insulation. Electrical rating, mechanical protection and reaction-to-fire classification remain separate requirements. Low-smoke halogen-free construction does not by itself establish operation during a fire.

N2XSH single-core cable cutaway and cross-section with a stranded copper conductor and copper wire screen
N2XSH construction illustration with copper conductor, screened insulation and outer sheath; not to scale.

건설

Phase conductor
Stranded copper, 수업 2
단열 시스템
XLPE between inner and outer semiconductive layers
금속 스크린
Copper wires; associated tape arrangement follows the declared design
Outer protection
Low-smoke, halogen-free sheath; unarmoured reference

형질

MV designations
6/10, 12/20 그리고 18/30 kV; voltage-specific constructions
Reference table
단일 코어 12/20 (24) kV, 95 에게 500 mm² selected sizes
설치
Fixed distribution, building supply and industrial cable routes
Performance basis
전기 같은, 연기, gas and flame tests assessed separately

N2XSH Project Enquiries

Discuss the voltage, conductor section, screen duty and fire-performance requirements with XWA.

견적 요청

낮은 연기, Halogen-Free and Flame Behaviour

A cable route through an occupied building or an enclosed service area can have different fire requirements from an external feeder. N2XSH addresses the sheath side of that specification while retaining the screened XLPE construction of an MV circuit. Its suitability depends on the complete declared design, not the abbreviation alone.

PropertyWhat it establishesWhat it does not establish
Smoke emissionSmoke behaviour under the specified cable-burning test, IEC와 같은 61034-2.No smoke under every possible fire condition.
Combustion gasesHalogen acid-gas assessment and acidity/conductivity assessment under the applicable IEC 60754 부분품.A universal absence of hazardous combustion products.
Flame propagationPerformance in the specified single-cable or bunched-cable test.Continued circuit operation while exposed to fire.
Declared fire classAn assessed reaction-to-fire classification for the documented product.A class automatically assigned to every cable called N2XSH.

공식 smoke-density test scope concerns smoke measurement under defined burning conditions. That evidence cannot substitute for an electrical circuit-integrity test. Emergency circuits with a specified survival time require the appropriate cable system and separate evidence.

N2XSH 12/20 kV Reference Dimensions

권장 참고자료. The table describes one published single-core copper construction with a copper wire screen. These dimensions and masses are not XWA guaranteed values or a confirmed supply range. Final cable data follows the approved manufacturing specification.

Conductor/screen
(mm²)
격리
(mm)
Over insulation
(mm)
Minimum sheath
(mm)
대략. 의
(mm)
대략. 대량의
(kg/km)
1 엑스 95/165.524.02.136.01965
1 엑스 120/165.526.02.138.02235
1 엑스 150/255.527.02.139.02630
1 엑스 185/255.529.02.141.03035
1 엑스 240/255.531.02.143.03600
1 엑스 300/255.533.02.146.04220
1 엑스 400/355.536.02.149.05230
1 엑스 500/355.540.02.152.06290

Each row is for 12/20 kV, maximum system voltage 24 kV. The screen section follows the slash; 1×240/25 has one 240 mm² phase conductor and a separate 25 mm² screen. Values from 6/10 또는 18/30 kV designs are not interchangeable with this table.

No universal ampacity is assigned here. The current rating depends on circuit arrangement, 스크린 본딩, surrounding temperature, soil or duct conditions and neighbouring heat sources. A project calculation and the approved cable construction are required; conductor area or sheath designation alone is insufficient.

The Two Diameters That Matter at a Termination

An MV termination interfaces with several surfaces, not just a nominal conductor size. The diameter over insulation sets one accessory interface; the complete cable diameter sets another at the outer entry or seal. A termination range and a cable gland range therefore refer to different dimensions.

In the selected 240/25 reference, the insulation diameter is 31 mm while the complete cable diameter is approximately 43 mm. 사용 43 mm to select an insulation interface confuses those surfaces. Manufacturing tolerances and the accessory’s own specified limits remain part of the fit assessment.

The semiconductive insulation screen also has its own preparation method. Strippable and bonded screen designs require the appropriate preparation procedure and tools. A cutaway illustration does not establish which removal method applies to the supplied cable.

Building Entry, Cable Trays and Protected Routes

Screened LSZH MV cables are relevant to industrial power distribution, substations and building feeders where the installation specification calls for controlled smoke and gas behaviour. A tunnel application requires the actual fire classification, route arrangement and local acceptance criteria; the word LSZH alone is not a tunnel approval.

An exterior-to-interior run can avoid an unnecessary sheath transition only when the same declared cable is suitable on both portions of the route. 자외선 노출, standing water, soil contact and fire requirements must all be covered. Some published N2XSH designs restrict outdoor or underground use to protected installation, so direct burial is not a model-wide promise.

The copper screen is not impact armour. 덕트, 커버, 쟁반, supports or another protection system may be necessary where the route exposes the cable to damage. Water-blocking properties likewise require a specified design; a halogen-free sheath does not provide the longitudinal barriers identified by an (에프) 변종.

Cable routing remains constrained by the stated installation bend radius, pulling method and support system. The supporting explanation of MV 케이블 굽힘 반경 및 인장 장력 separates these handling limits from the electrical rating.

N2XSH, N2XSY and N2XS2Y

모델Outer-sheath distinctionRelevant specification difference
N2XSHLow-smoke, halogen-free sheathFire-test performance and installation suitability must be defined for the exact construction.
N2XSY cablePVC sheathPVC and LSZH have different combustion-gas and material characteristics.
N2XS2Y cablePE 외장PE sheath protection does not by itself imply a flame-retardant, low-smoke construction.
N2XS(에프)시간 / N2XS(플로리다)시간Halogen-free sheath with additional water barriers(에프) identifies longitudinal water blocking; (플로리다) additionally identifies a radial moisture barrier in the specified design.

The comparison concerns copper screened MV constructions. An aluminium-conductor NA2XSH design changes the phase-conductor material as well. Three-core N2XSEH places three screened phase cores inside a common sheath and needs its own dimensional and rating data.

Electrical Tests and Fire Evidence Have Different Jobs

IEC 60502-2 addresses extruded-insulation power cables within its MV scope. HD 622 / DIN VDE 0276-622 also appears in established halogen-free MV constructions. The agreed manufacturing standard and voltage designation must identify the actual design; listing several references does not establish simultaneous conformity.

도체 저항, insulation tests, partial-discharge assessment and oversheath tests relate to different electrical or material requirements. The applicable standard determines their method and acceptance limits. Routine production records are not interchangeable with a type-test report, and neither should be inferred from a product illustration.

For fire performance, the report or declaration must identify the assessed construction and the applicable method. A third-party catalogue’s class, certificate or laboratory accreditation cannot be carried over to another manufacturer. The product description here does not claim an XWA CPR class or circuit-survival rating.

N2XSH Cable Questions

Can N2XH replace medium-voltage N2XSH?

아니요, not on sheath material alone. The MV construction described here includes electrical screens and voltage-specific insulation. A low-voltage N2XH cable does not become an MV cable because both designs use XLPE and a halogen-free sheath.

Does N2XSH automatically have a B2ca classification?

아니요. A reaction-to-fire class belongs to an assessed product construction and its supporting documentation. The N2XSH designation alone does not assign B2ca or any smoke, droplet or acidity subclass.

무엇을 3 엑스 1 엑스 240/25 mean for this cable?

It describes three separate single-core cables, each with a 240 mm2 phase conductor and a 25 mm2 metallic screen. It is not one three-core cable under a common sheath. Phase arrangement and screen bonding still need their own design.

Is the copper wire screen mechanical armour?

아니요. The metallic screen has electrical screening and specified earth-fault duties. It must not be treated as wire armour against impact or excavation damage. Mechanical protection follows the installation route and declared cable construction.