N2XSEY Cable

N2XSEY cable is a three-core medium-voltage power cable with stranded copper conductors, screened XLPE insulation and a common PVC outer sheath. Three phase cores form one assembled cable for fixed distribution.

The reference CU/XLPE/CTS/PVC construction uses metallic screening but no armour. The shared sheath distinguishes it from a circuit of three separate single-core cables and changes handling mass, cable-entry dimensions and installation geometry.

Concept illustration of three individually screened copper cores within a common PVC cable sheath
Three screened copper cores inside one PVC sheath. Concept illustration, not to scale.

CONSTRUCTION

Conducteurs
Three stranded copper phase conductors
Insulated cores
Semiconductive screens and XLPE insulation
Écrans métalliques
Copper tape screening in the reference construction
Assembly
Filler and common PVC sheath; non blindé

CARACTÉRISTIQUES

Reference voltage
12/20 kV for the displayed dataset
Core layout
Three screened cores in one cable body
Thermal reference
90°C maximum operating conductor temperature in the source design
Standard context
CEI 60502-2 and relevant VDE/HD project requirements

N2XSEY for Fixed Power Distribution

Tension, conductor/screen size and route conditions define the project configuration.

Demander un devis

N2XSEY Cable Technical Data

Recommended reference data. Final dimensions and ratings follow the approved project configuration; the selected rows are not a confirmed XWA production range.

Taille du câble
(mm²)
Résistance CC
20°C (Ω/km)
Environ. DE
(mm)
Environ. masse
(kg/km)
Air
(UN)
Ground
(UN)
3 x 95/160.193067.06900326316
3 x 150/250.124074.59250426404
3 x 185/250.099178.510650488457
3 x 240/250.075485.013000576532
3 x 300/250.060190.015250654599
3 x 400/350.047098.019100750685

Three-core CU/XLPE/CTS/PVC, 12/20 kV. Mass and diameter describe the assembled cable. The /screen notation does not create a fourth phase core; the approved drawing defines the screen arrangement.

Reference ampacity: one system; air 30°C, facteur de charge 1.0; ground 20°C, profondeur 0.7 m, résistivité thermique 1.0 K·m/W, facteur de charge 0.7. Reference conductor limit: 90°C. The buried ratings do not represent a continuously fully loaded circuit at load factor 1.0.

Three-core construction and accessory interfaces

A single overall sheath fixes the relative positions of the three phase cores. Three separate single-core cables permit a chosen flat or trefoil arrangement. Equal voltage and conductor area do not make their current-rating or handling data interchangeable.

Termination stress-control components fit the insulation diameter and screen treatment. Glands and entry seals fit the complete cable diameter. The 3×240/25 reference is approximately 85 mm in diameter and 13 kg/m, before drum tare; handling calculations therefore use assembly mass, not copper mass alone.

Schematic of three individually screened copper cores, Isolation XLPE, filler and common PVC sheath
Three screened cores share one outer sheath; the drawing is explanatory and not to scale.
Diagram separating cable voltage designation from insulation diameter and overall diameter for accessory fit
Voltage class alone does not establish termination, joint or gland compatibility.

Applications and Installation Conditions

Distribution industrielle, substation connections and underground or ducted feeder sections can suit a combined three-core assembly. Pulling equipment, route access and bending limits must fit the complete cable. Armure, water blocking and enhanced fire-performance sheaths require separately identified constructions rather than assumptions about the N2XSEY name.

The production definition must identify screen arrangement, insulation and sheath thicknesses, accessory diameters and applicable tests for the assembled three-core cable. The official standard scope concerns fixed distribution installations, not an automatic claim of approval for special service.

N2XSEY and Related Constructions

ModèleMain difference
N2XSY single-core cableEach phase cable has its own sheath; circuit geometry and bonding need separate assessment.
20 Gamme de câbles kVVoltage-class context for 12/20(24) kV projects, rather than an exact three-core model.
Armoured MV constructionMechanical armour adds a separate layer and changes the specified design and dimensions.

N2XSEY Cable FAQs

Does N2XSEY mean the cable is armoured?

Non. The reference screened construction is unarmoured. A metallic screen provides an electrical function and is not mechanical armour.

Can 12/20 kV dimensions be used for a 6/10 kV variant?

Non. The values here belong only to the stated 12/20 construction kV. A different voltage design needs its own dimensional and rating data.

Is N2XSEY the same as three N2XSY cables?

Non. N2XSEY combines three phase cores within one sheath. Separate N2XSY cables have different assembly, handling and installation arrangements.