Câble N2XS2Y

Câble N2XS2Y is a single-core medium-voltage power cable with a stranded copper conductor, Isolation XLPE, copper wire screen and polyethylene outer sheath.

The designation is used for fixed medium-voltage distribution where a PE-sheathed cable is preferred for underground, water-exposed, de plein air, duct and demanding utility routes. Les classes de tension courantes du projet incluent 6/10 kV, 8.7/15 kV, 12/20 kV et 18/30 kV selon les spécifications orientées CEI et VDE.

XWA supplies N2XS2Y as a project cable configuration where conductor size, section d'écran en cuivre, classe de tension, PE sheath requirement, les documents de test et l'emballage d'exportation sont adaptés au calendrier des câbles et au marché de destination.

Câble N2XS2Y

CONSTRUCTION

Conducteur:

Classe 2 conducteur en cuivre toronné, rond compacté là où spécifié

Isolation:

Isolation XLPE avec écrans semi-conducteurs intérieurs et extérieurs

Écran métallique:

Écran en fil de cuivre avec contre-hélice; screen section selected by fault-current requirement

Gaine extérieure:

Polyethylene outer sheath, généralement noir; MDPE or HDPE direction follows the project specification

CARACTÉRISTIQUES

Classes de tension:

6/10 kV, 8.7/15 kV, 12/20 kV et 18/30 Classes de projets kV

Température du conducteur:

Les conceptions moyenne tension XLPE utilisent couramment 90°C maximum conductor temperature in normal service

Installation:

Installation fixe en intérieur, en plein air, in ducts and in ground routes with suitable mechanical and thermal design

NORMES:

Les références courantes incluent la CEI 60502-2, VDE 0276-620, CEI 60228 et CEI 60332-1-2. La référence standard n'est pas une revendication de certification.

N2XS2Y Medium Voltage Cable for Utility and Industrial Networks

XWA manufactures medium-voltage cable configurations for distribution networks, sous-stations, routes des énergies renouvelables et alimentations industrielles.

N2XS2Y Cable Technical Data

Données de référence recommandées: N2XS2Y is normally a single-core screened medium-voltage cable. Le format de taille ci-dessous est la section du conducteur / section de l'écran en cuivre en mm2.

Les valeurs d'intensité admissible sont des valeurs de référence pour un circuit unipolaire dans l'air à 30°C with load factor 1.0 and three-cable bunching, or in ground at 20°C with load factor 0.7 and three-cable bunching. La cote actuelle du projet final dépend de la résistivité thermique du sol, profondeur d'enfouissement, espacement, regroupement, collage de gaine, température de l'itinéraire et méthode de calcul locale. Les dimensions finales de fabrication XWA et les valeurs de test suivent la fiche technique du devis approuvé..

N2XS2Y 6/10 Données recommandées en kV

Classe de tensionTaille du câbleConductor resistance at 20 C (ohms/km)Épaisseur de l'isolation (mm)PE sheath thickness (mm)Environ. DE (mm)Environ. poids (kg/km)Capacité dans l'air 30 C (UN)Capacité dans le sol 20 C (UN)
6/10 kV1 x 35/160.5243.42.524900197187
6/10 kV1 x 50/160.3873.42.525950236220
6/10 kV1 x 70/160.2683.42.5271200294268
6/10 kV1 x 95/160.1933.42.5281450358320
6/10 kV1 x 120/160.1533.42.5301700413363
6/10 kV1 x 150/250.1243.42.5312050470409
6/10 kV1 x 185/250.09913.42.5332400535456
6/10 kV1 x 240/250.07543.42.5352950631526
6/10 kV1 x 400/350.04703.42.5414500827662

N2XS2Y 12/20 Données recommandées en kV

Classe de tensionTaille du câbleConductor resistance at 20 C (ohms/km)Épaisseur de l'isolation (mm)PE sheath thickness (mm)Environ. DE (mm)Environ. poids (kg/km)Capacité dans l'air 30 C (UN)Capacité dans le sol 20 C (UN)
12/20 kV1 x 35/160.5245.52.528970200189
12/20 kV1 x 50/160.3875.52.5291150239222
12/20 kV1 x 70/160.2685.52.5311350297271
12/20 kV1 x 95/160.1935.52.5321650361323
12/20 kV1 x 120/160.1535.52.5341900416367
12/20 kV1 x 150/250.1245.52.5352250470409
12/20 kV1 x 185/250.09915.52.5372600538461
12/20 kV1 x 240/250.07545.52.5403200634532
12/20 kV1 x 400/350.04705.52.5454750829671

N2XS2Y 18/30 Données recommandées en kV

Classe de tensionTaille du câbleConductor resistance at 20 C (ohms/km)Épaisseur de l'isolation (mm)PE sheath thickness (mm)Environ. DE (mm)Environ. poids (kg/km)Capacité dans l'air 30 C (UN)Capacité dans le sol 20 C (UN)
18/30 kV1 x 50/160.3878.02.5341350241225
18/30 kV1 x 70/160.2688.02.5361600299274
18/30 kV1 x 95/160.1938.02.5371900363327
18/30 kV1 x 120/160.1538.02.5392150418371
18/30 kV1 x 150/250.1248.02.5402550472414
18/30 kV1 x 185/250.09918.02.5422900539466
18/30 kV1 x 240/250.07548.02.5443500635539

N2XS2Y Cable Construction

N2XS2Y is built around a stranded copper conductor with an extruded conductor screen, Isolation XLPE et écran isolant appliqué dans le cadre du système d'isolation moyenne tension. Un écran en fil de cuivre et une contre-hélice assurent le chemin de l'écran métallique, followed by a polyethylene outer sheath.

La construction monocœur est importante. Note actuelle, collage d'écran, tension de gaine induite, le rayon de courbure et la conception des terminaisons sont évalués différemment du câble MT à trois conducteurs. Lorsqu'un appel d'offres nécessite un câble blindé à trois conducteurs, N2XSEY ou une autre désignation à trois cœurs pourrait être la meilleure solution.

La section d'écran en cuivre, communément affiché comme le deuxième nombre dans une taille telle que 1 x 240/25 mm2, est sélectionné en fonction du courant de défaut à la terre et de la conception de la protection. Il n'est pas décoratif et doit correspondre aux besoins en courant de défaut du système..

Applications for N2XS2Y Medium Voltage Cable

N2XS2Y cable is used in medium-voltage distribution networks where a screened single-core cable with PE sheath is accepted by the project specification. Les itinéraires courants incluent les postes de transformation, postes de commutation, centrales électriques, mangeoires industrielles, réseaux de collecte d'énergies renouvelables et circuits de distribution de services publics.

Le câble peut être installé à l'intérieur, en plein air, in ducts, in water and in ground routes when the installation design accounts for mechanical protection, tirer la tension, rayon de courbure, température de l'itinéraire et courant nominal. The PE sheath supports stronger mechanical and moisture-resistance positioning than a conventional PVC sheath.

The PE sheath is not normally treated as a flame-retardant sheath under flame-test definitions used for PVC-sheathed cable. Pour les tunnels, public buildings or routes requiring flame-retardant or low-smoke halogen-free performance, another MV cable design may be required.

N2XS2Y vs N2XSY, NA2XS2Y and N2XS(F)2Y

N2XS2Y and N2XSY share copper conductor, XLPE insulation and screened single-core MV cable logic, but the outer sheath differs. N2XSY uses PVC sheath; N2XS2Y uses PE sheath for routes where mechanical durability, water exposure or underground service is a stronger requirement.

NA2XS2Y is the aluminium-conductor companion to N2XS2Y. It can reduce conductor cost and weight, but conductor size, résistance, termination design and short-circuit performance are different from copper N2XS2Y.

N2XS(F)2Y adds a longitudinal water-blocking construction detail. It should not be treated as identical to standard N2XS2Y unless the project specification requires the `(F)` water-blocking layer and XWA confirms that construction.

ModèleDistinction principaleRôle de page typique
N2XSYCopper conductor with PVC sheathPVC-sheath comparison
N2XS2YCopper conductor with PE sheathCette page
NA2XS2YAluminium conductor with PE sheathNext companion page
N2XS(F)2YCopper conductor with PE sheath and longitudinal water blockingSeparate water-blocked variant

Essai, Documents et emballage d'exportation

N2XS2Y production documentation can include the approved datasheet, contrôles de résistance des conducteurs, enregistrements de tests de tension, enregistrements de tests de décharge partielle, contrôle dimensionnel, programme de batterie, liste de colisage et photos du produit. Essais de types, les preuves de test de flamme ou d'inspection par un tiers sont ajoutées uniquement lorsque cela est requis par le projet et disponibles pour la construction exacte.

L'emballage à l'exportation est normalement planifié par poids de câble, longueur du tambour, diamètre maximum du tambour, manutention des itinéraires et chargement des conteneurs. Les câbles unipolaires moyenne tension peuvent devenir lourds en cas de sections importantes, la longueur du tambour fait donc partie de l'examen technique et logistique, pas seulement une préférence d'expédition.

Pour devis, XWA a besoin de la désignation du modèle, classe de tension, taille du conducteur, section d'écran en cuivre, itinéraire d'installation, standard, quantité, longueur de tambour préférée, pays de destination et documents requis. Les informations sont utilisées pour confirmer la configuration du câble et émettre une offre spécifique au projet.

N2XS2Y Cable FAQs

What is N2XS2Y Cable?

N2XS2Y Cable is a screened single-core medium-voltage power cable with a copper conductor, Isolation XLPE, copper wire screen and polyethylene outer sheath. Il est utilisé pour les itinéraires de distribution MT fixes dans les services publics., sous-station, systèmes industriels et de production.

Common N2XS2Y voltage classes include 6/10 kV, 8.7/15 kV, 12/20 kV et 18/30 kV. Le calendrier des câbles du projet définit la classe de tension Uo/U requise et les exigences de tension d'essai..

La construction typique est la classe 2 conducteur en cuivre toronné, écran conducteur, Isolation XLPE, écran isolant, copper wire metallic screen with counter helix and PE outer sheath. The screen section and sheath material are specified by the project.

N2XS2Y is normally a single-core medium-voltage cable. Les exigences MT à trois conducteurs doivent être vérifiées séparément car la conception du câble, disposition des écrans, le rayon de courbure et les accessoires sont différents.

Dans une taille telle que 1 x 240/25 mm2, 240 mm2 is the copper conductor cross-section and 25 mm2 est la section transversale de l'écran en cuivre. La valeur de l'écran doit correspondre au service de mise à la terre et à la conception de la protection.

N2XS2Y is used in transformer stations, postes de commutation, centrales électriques, réseaux de distribution industrielle, circuits de collecte d'énergies renouvelables, cable ducts and underground utility routes where PE-sheathed MV cable is accepted.

N2XS2Y utilise une gaine extérieure en PE. N2XSY uses a PVC outer sheath. PE sheath can be preferred for underground, water-exposed or mechanically demanding routes, while PVC sheath remains common where flame behaviour, la manipulation ou la convention du projet pointe vers le PVC.

N2XS(F)2Y adds longitudinal water-blocking layers around the metallic screen area. Standard N2XS2Y should not be described as an `(F)` water-blocked cable unless that construction is specified and confirmed.

N2XS2Y can be installed in ground or water-exposed routes when the cable design, la protection des itinéraires et les règles locales le permettent. Le courant nominal et la durée de vie dépendent de la profondeur d'enfouissement, résistivité thermique du sol, espacement, regroupement, humidité et protection mécanique.

Pour un devis de projet, XWA needs the N2XS2Y voltage class, taille du conducteur, section d'écran en cuivre, standard, itinéraire d'installation, quantité, longueur du tambour, pays de destination et documents d’inspection ou d’essai requis.

Câble d'alimentation moyenne tension blindé MT

Câble d'alimentation MT

Systèmes de câbles moyenne tension pour la distribution, sous-stations et départs industriels.

11Structure du câble kV

11Câble kV

Page des câbles moyenne tension pour la distribution 11 kV et les calendriers de câbles du projet.

Études de cas XWA & Projets

    Obtenez un devis gratuit en 24 Heures

    E-mail*:

    Nom*:

    Votre pays:

    Tél*:

    Vos exigences*: