Cable NYY-J 0.6/1 kV PVC Insulated Copper Power Cable

Cable NYY-J is a copper-conductor power cable with PVC insulation and a PVC outer sheath. It is designed for fixed low-voltage distribution in buildings, instalaciones industriales, utility systems, cable ducts and underground routes.

The J suffix identifies a green/yellow protective conductor within the cable. NYY-O is the related version without a green/yellow protective conductor. Black PVC sheathing provides a durable finish for general indoor, outdoor and buried fixed installations.

Cable NYY-J 0.6/1 kV PVC power cable reference

CONSTRUCCIÓN

Conductor:

Conductor de cobre, solid or stranded according to cable size

Aislamiento:

Aislamiento de PVC

Identificación central:

NYY-J includes a green/yellow protective conductor; NYY-O does not

Funda exterior:

cubierta exterior de PVC, commonly black

CARACTERÍSTICAS

Clasificación de voltaje Uo/U:

0.6/1 kV

Conductor Temperature:

Maximum conductor temperature: 70°C under normal operation

Instalación:

Fixed indoor, exterior, duct and underground installation

NORMAS:

VDE 0276-603 / alta definición 603, IEC 60502-1 y IEC 60228

NYY-J Cable for Fixed Low-Voltage Distribution

XWA supplies NYY-J power cable in multicore configurations for building, industrial and infrastructure systems.

NYY-J Cable Technical Data

Recommended Reference Data: The tables cover common 2-core, 3-centro, 4-core and 5-core NYY-J 0.6/1 kV constructions. The stated core count includes the green/yellow protective conductor.

Current ratings use the reference conditions: 30°C ambient air, 15°C ground temperature, 0.5 m laying depth and soil thermal resistivity of 1.2 K m/W. Values are recommended reference data, not guaranteed XWA production values. Final dimensions, weights and ratings follow the approved XWA datasheet and installation calculation.

2-Core NYY-J Recommended Data

Cores x mm2Conductormáx.. DC resistance at 20 C (ohm/km)Aislamiento (mm)Vaina (mm)Aprox.. OD (mm)Aprox.. peso (kg/km)In duct (A)In air (A)
2 incógnita 2.5RE / Clase 17.410.81.810.71794227
2 incógnita 4RM / Clase 24.611.01.813.02685437
2 incógnita 6RM / Clase 23.081.01.814.23376848
2 incógnita 10RM / Clase 21.831.01.816.24729066
2 incógnita 16RM / Clase 21.151.01.818.264411689

3-Core NYY-J Recommended Data

Cores x mm2Conductormáx.. DC resistance at 20 C (ohm/km)Aislamiento (mm)Vaina (mm)Aprox.. OD (mm)Aprox.. peso (kg/km)In duct (A)In air (A)
3 incógnita 1.5RE / Clase 112.10.81.810.41662618
3 incógnita 2.5RE / Clase 17.410.81.811.32123425
3 incógnita 4RE / Clase 14.611.01.813.12994434
3 incógnita 6RE / Clase 13.081.01.814.23805643
3 incógnita 10RM / Clase 21.831.01.817.15707560
3 incógnita 16RM / Clase 21.151.01.819.27899880
3 incógnita 25RM / Clase 20.7271.21.822.11141128106
3 incógnita 35RM / Clase 20.5241.21.824.11462157131
3 incógnita 50RM / Clase 20.3871.41.827.61964185159
3 incógnita 95RM / Clase 20.1931.62.240.04488275244

4-Core NYY-J Recommended Data

Cores x mm2Conductormáx.. DC resistance at 20 C (ohm/km)Aislamiento (mm)Vaina (mm)Aprox.. OD (mm)Aprox.. peso (kg/km)In duct (A)In air (A)
4 incógnita 1.5RE / Clase 112.10.81.811.61982618
4 incógnita 2.5RE / Clase 17.410.81.812.12523425
4 incógnita 4RE / Clase 14.611.01.814.03554434
4 incógnita 6RE / Clase 13.081.01.815.44655643
4 incógnita 10RM / Clase 21.831.01.818.67027560
4 incógnita 16RM / Clase 21.151.01.821.19929880
4 incógnita 25RM / Clase 20.7271.21.824.21431128106
4 incógnita 35RM / Clase 20.5241.21.826.61861157131
4 incógnita 50RM / Clase 20.3871.41.930.92535185159
4 incógnita 70RM / Clase 20.2681.42.135.13441252247
4 incógnita 95RM / Clase 20.1931.62.240.44691303305
4 incógnita 120RM / Clase 20.1531.62.444.25757313282
4 incógnita 150RM / Clase 20.1241.82.548.57095390407
4 incógnita 185RM / Clase 20.09912.02.753.98810399371
4 incógnita 240RM / Clase 20.07542.22.961.111400464436

5-Core NYY-J Recommended Data

Cores x mm2Conductormáx.. DC resistance at 20 C (ohm/km)Aislamiento (mm)Vaina (mm)Aprox.. OD (mm)Aprox.. peso (kg/km)In duct (A)In air (A)
5 incógnita 1.5RE / Clase 112.10.81.812.02322418
5 incógnita 2.5RE / Clase 17.410.81.813.13023425
5 incógnita 4RE / Clase 14.611.01.815.24284434
5 incógnita 6RE / Clase 13.081.01.816.55515643
5 incógnita 10RM / Clase 21.831.01.820.38537560
5 incógnita 16RM / Clase 21.151.01.823.112129880
5 incógnita 25RM / Clase 20.7271.21.826.61759128106
NYY-J multicore PVC cable construction reference
Multicore PVC-insulated and PVC-sheathed power cable reference.
NYY-J cable drum packing
Cable drum packing used for low-voltage power cable transport and storage.

NYY-J Cable Applications

NYY-J cable is used for fixed power distribution where a conventional PVC-insulated and PVC-sheathed cable matches the installation environment.

  • Commercial and residential building feeders.
  • Plantas industriales, workshops and utility rooms.
  • Distribution boards and fixed equipment connections.
  • Cable ducts, conduits and protected outdoor routes.
  • Underground power distribution with suitable route protection.

NYY-J is unarmoured. Routes exposed to impact, crushing or excavation damage use ducts, covers or a separate armoured cable construction.

NYY-J vs NYY-O and N2XY Cable

NYY-J and NYY-O share the same PVC-insulated, PVC-sheathed construction. The suffix identifies whether a green/yellow protective conductor is included.

CaracterísticaNYY-JNYY-ON2XY
AislamientoCLORURO DE POLIVINILOCLORURO DE POLIVINILOXLPE
Outer sheathCLORURO DE POLIVINILOCLORURO DE POLIVINILOCLORURO DE POLIVINILO
Protective conductorIncludedNot includedJ or O versions
Normal conductor temperature70°C70°C90°C
Main distinctionGreen/yellow PE coreNo green/yellow PE coreHigher-temperature XLPE insulation

N2XY is the related XLPE-insulated alternative. Its common 90°C conductor rating differs from the 70°C PVC-insulated NYY construction.

NYY-J Cable Performance and Installation

PVC insulation and sheathing provide a practical cable construction for general low-voltage distribution. Current-carrying capacity varies with conductor size, core loading, ambient temperature, grouping and installation method.

The black outer sheath is commonly used for outdoor and underground routes. Environmental performance, bending radius and pulling force are defined by the finished cable construction.

NYY-J is not an armoured or LSZH cable. Mechanical protection and fire-performance requirements can lead to a different cable design, such as an armoured power cable or a halogen-free model.

NYY-J Cable fixed building installation
Fixed low-voltage power cable installation in building infrastructure.

NYY-J Cable Technical FAQs

What does NYY-J Cable mean?

In the VDE-style designation, N identifies a cable made to a recognized national standard, the first Y indicates PVC insulation, the second Y indicates a PVC outer sheath, and J indicates that the cable includes a green/yellow protective conductor.

NYY-J is used for fixed low-voltage distribution in buildings, instalaciones industriales, utility systems, cable ducts and underground routes. It is not designed for continuous movement or portable equipment.

NYY-J is commonly specified for 0.6/1 kV service with copper Class 1 o clase 2 conductores, Aislamiento de PVC, PVC filling or inner covering, and a black PVC outer sheath. Normal conductor temperature is commonly 70°C. Referenced standards include VDE 0276-603 / alta definición 603, IEC 60502-1 y IEC 60228.

The recommended tables cover 2-core, 3-centro, 4-core and 5-core NYY-J constructions. The stated core count includes the green/yellow protective conductor. Covered reference ranges are 2 incógnita 2.5 a 2 incógnita 16 mm², 3 incógnita 1.5 a 3 incógnita 95 mm², 4 incógnita 1.5 a 4 incógnita 240 mm², y 5 incógnita 1.5 a 5 incógnita 25 mm².

NYY-J current carrying capacity changes with cross-section, core count and installation method. In the recommended table, 3 incógnita 1.5 mm² is rated at 26 A in duct and 18 A in air, mientras 4 incógnita 240 mm² is rated at 464 A in duct and 436 A in air. These reference values use 30°C ambient air, 15°C ground temperature, 0.5 m laying depth and 1.2 K m/W soil thermal resistivity; other conditions require correction factors or a separate calculation.

NYY-J is used in fixed outdoor and underground installations where the cable specification and local installation rules permit. Its PVC sheath suits general environmental exposure, but the cable is unarmoured. Ducts, covers or other mechanical protection are used where impact, crushing or excavation damage is possible.

NYY-J includes a green/yellow protective conductor. NYY-O has no green/yellow protective conductor. The conductor, PVC insulation and PVC sheath construction are otherwise generally comparable within the same specification.

NYY-J is a 0.6/1 kV PVC-insulated, PVC-sheathed power cable commonly used for fixed indoor, outdoor and underground distribution. NYM-J is generally a 300/500 V building installation cable for fixed wiring in or around plaster, masonry and similar building routes. NYM-J outdoor and underground suitability is more restricted and depends on its exact product specification.

Cable N2XOH Cable de alimentación de bajo voltaje LSZH estándar de la UE

Cable N2XOH

Halogen-free low-smoke power cable for fixed building and infrastructure installations.

Cable de baja tensión BT

Cable de baja tensión

Low-voltage cable constructions for building, industrial and utility distribution.