N2XS(F)2Y Cable

N2XS(F)2Y cable is a screened single-core copper MV power cable with XLPE insulation, una pantalla de alambre de cobre, longitudinal water-blocking components and a PE outer sheath for fixed distribution.

The copper conductor carries load current; the surrounding screen performs a separate electrical duty. Industrial feeders, substation circuits and underground networks use this construction where the voltage, bonding arrangement and route conditions match the cable-system design.

Copper single-core XLPE cable cutaway showing the conductor, copper wire screen and black PE sheath
Single-core copper cable construction with metallic screening. Ilustración.

CONSTRUCCIÓN

Conductor
Cobre trenzado
Aislamiento
XLPE entre conductor semiconductor y pantallas de aislamiento.
Región de la pantalla
Copper wires and tape; longitudinal water-blocking components
Funda exterior
Black PE; no armour in the reference construction

CARACTERÍSTICAS

Tensión de referencia
12/20 (24) kV
Core configuration
Un solo núcleo; separate conductor and screen areas
Thermal reference
90°C maximum operating conductor temperature in the source design
Contexto estándar
alta definición 620 / DIN VDE 0276-620; agreed project requirements

N2XS(F)2Y for Fixed Power Distribution

Voltaje, conductor/screen size and route conditions define the project configuration.

Solicitar una cotización

N2XS(F)2Datos técnicos del cable Y

Datos de referencia recomendados: published values for preliminary comparison. Final supply dimensions, ratings and size range follow the agreed XWA datasheet.

Tamaño del cable
(mm²)
resistencia CC
20°C (Ω/km)
Aislamiento
(mm)
Aprox.. DE
(mm)
Aprox.. masa
(kg/km)
Aire
(A)
Suelo
(A)
1 incógnita 95/160.1935.5321580361323
1 incógnita 150/250.1245.5352212470409
1 incógnita 240/250.0755.5393181634532
1 incógnita 300/250.0605.5423851724599
1 incógnita 400/350.0475.5444795829671
1 incógnita 500/350.0375.5475873953754

Copper single-core N2XS(F)2Y, 12/20 kV, Pantalla de alambre de cobre y funda de PE.. The listed dimensions, mass and current ratings apply to this reference construction and the installation conditions below.

Ampacity basis: un circuito en contacto con el trébol, pantallas sólidamente adheridas; aire 30°C sin sol directo; ground 20°C at 0.7 m depth. Source assumptions include 1.0 K·m/W wet soil and 2.5 K·m/W dry soil, with no additional heat sources. Límite del conductor de referencia: 90°C.

Conductor de cobre, metallic screen and the (F) designación

In a reference 1×240/25 construcción, 240 mm² belongs to the phase conductor and 25 mm² to the metallic screen. Screen fault-current duty, protection clearing time and accessory connections are separate from continuous conductor ampacity.

El (F) construction restricts water travel along the specified cable region. N2XS(Florida)2Y adds a laminated metallic barrier beneath the PE sheath to reduce radial moisture ingress.

Single-core copper cable diagram explaining a 240 mm2 conductor and a separately specified 25 pantalla metalica mm2
The conductor area and screen area are separate specification entries.
Comparison of ordinary PE sheath, longitudinal water blocking and a longitudinal plus radial barrier construction
El (F) version provides longitudinal blocking; (Florida) adds a radial laminate beneath the PE sheath.

Applications and Installation Conditions

Typical routes include industrial power intake, substation feeders and underground distribution. Protección mecánica, requisitos contra incendios, moisture exposure and accessory interfaces are specified for the installation.

The test schedule covers conductor resistance, aislamiento, sheath integrity and the specified longitudinal water-blocking performance. Screen connections and accessory interfaces complete the system design. The IEC publication scope describes the fixed-installation framework.

N2XS(F)2Y and Related Constructions

ModeloMain difference
Cable N2XS2YConductor de cobre, XLPE insulation and PE sheath; longitudinal water blocking is not specified by the N2XS2Y designation.
Cable N2XSYCopper screened MV cable with PVC outer sheath.
N2XS(Florida)2YCombines longitudinal water blocking with a laminated metallic barrier beneath the PE sheath for radial moisture protection.

N2XS(F)2Preguntas frecuentes sobre cables en Y

Are N2XS(F)2Y and N2XS2Y interchangeable?

El (F) version adds longitudinal water-blocking components to the screened cable construction. The project moisture requirements determine whether this feature is needed.

What does 1×240/25 identify?

It identifies one 240 mm² phase conductor and a separately specified 25 pantalla metálica mm².

Can the displayed ampacity be used for ducts?

The displayed values use the stated trefoil, Unión y condiciones térmicas.. Ducts and grouped circuits require a calculation for their own surrounding materials and installation geometry.