XLPE/SWA/PVC-Kabel

XLPE/SWA/PVC cable combines XLPE insulation, steel wire armour and a PVC outer sheath for fixed power distribution. The construction can use copper or aluminium conductors, with insulation and electrical screens selected for the rated voltage.

For fixed industrial feeders, underground distribution and project power routes, the armour adds mechanical protection while the insulation system carries the electrical duty. XWA Power & Cable is a cable manufacturer in China; explore our factory and production information or send a cable schedule for a project quotation.

Orange-sheathed four-core copper cable sample marked XLPE/SWA/PVC 0.6/1 kV 4X25 with exposed wire armour
Real sample marked XLPE/SWA/PVC 0.6/1 kV 4X25; other voltage designs have different layer arrangements.

XLPE/SWA/PVC for Your Project

Send the voltage, Leitermaterial, core size and required length, or attach your existing cable schedule.

Fordern Sie ein Angebot an

XLPE Insulation, Steel Wire Armour and PVC Sheath

In CU/XLPE/PVC/SWA/PVC, the layers run from copper conductor through XLPE insulation, PVC bedding and steel wire armour to the PVC outer sheath. Fillers support the assembled cores, while screened MV designs add the required electrical layers.

KomponenteFunction in the cableSpecification that changes the design
Copper or aluminium conductorTrägt LaststromMaterial, Bereich, conductor class and core arrangement
XLPE-IsolierungProvides electrical insulation around each phase conductorRated voltage and declared insulation thickness
Elektrische Bildschirme, wo erforderlichControl the electric field and provide the specified metallic-screen functionSemiconductive layers, screen material, area and fault duty
Bettwäsche oder InnenhülleSeparates the laid-up cores and armourMaterial, thickness and compatibility with the assembly
Panzerung aus StahldrahtAdds a layer of mechanical protectionWire diameter, Abdeckung, corrosion protection and termination arrangement
PVC-AußenmantelCovers the armoured assemblyCompound, thickness and declared environmental or fire performance

What Changes Between Voltage Classes

Steel wire armour provides mechanical protection across different voltage classes. The insulation and screening system is designed for the rated voltage.

Construction groupRepresentative configurationProject role
Low-voltage powerMulticore CU or AL / XLPE / Bettwäsche / SWA / PVC; 0.6/1 kV is one common exampleFixed plant feeders, distribution circuits and protected outdoor routes
MittelspannungsverteilungThree screened XLPE cores, metallische Bildschirme, inner sheath, SWA and PVC; examples include 6/10 Und 12/20 kV designsIndustrial intake, transformer feeders and distribution networks
High-voltage and special armoured systemsFull project-specific electrical, metallic-sheath, armour and outer-protection designTransmission and special-service routes requiring a separate cable-system review

In screened MV cable, semiconductive layers control the electric field and the metallic screen performs its specified electrical duty. These sit inside the bedding, armour and outer sheath.

High-voltage armoured systems require a dedicated insulation, Screening, sheath and armour design. Specialised submarine systems also address marine installation loads, moisture protection and accessories.

Abgeschnittenes Ende eines vieradrigen Kupferkabels mit farbiger Aderisolierung und einem Ring aus Panzerdrähten
Four-core cable cross-section with copper conductors and steel wire armour.

Armour selection for single-core AC circuits

Steel is ferromagnetic. Applying ordinary steel wire armour around a single AC phase can introduce additional magnetic losses and heating. Single-core AC power cables commonly use non-magnetic armour such as aluminium wire armour (AWA), while SWA is common around multicore assemblies.

Conductor and armour materials are separate choices: a copper conductor can have aluminium wire armour. Special HV, DC and unusual armour arrangements are assessed for their losses, bonding and mechanical duty.

Technical Scope and Standards

Design itemLow-voltage exampleScreened medium-voltage example
Nennspannung U0/U0.6/1 kV reference construction6/10 oder 12/20 kV reference construction; system requirements govern selection
DirigentenCopper or aluminium; conductor class declared on the datasheetCopper or aluminium; conductor and metallic-screen areas specified separately
IsoliersystemXLPE insulated cores with the declared bedding arrangementXLPE with semiconductive screens and the declared metallic screen
Standard contextIEC 60502-1 wo angegebenIEC 60502-2 wo angegeben
Final dimensional dataKernanzahl, Isolierung und Manteldicke, armour wires, OD and massThe same items plus screened-core and accessory interface dimensions
Aktuelle BewertungInstallation-specific calculation or matched datasheet conditionsInstallation, screen/armour losses, bonding and thermal conditions

The configurations shown illustrate the construction family. Endgültige Abmessungen, ratings and supply scope follow the agreed XWA datasheet for the selected voltage, core arrangement and materials.

IEC 60228 addresses conductors; IEC 60502-1 und IEC 60502-2 cover their respective LV and MV power-cable ranges. IEC 60840 provides the framework for higher-voltage systems within its scope. Der offizieller Veröffentlichungsbereich describes the MV standard coverage.

Underground and Industrial Route Conditions

SWA provides integral mechanical protection for industrial feeders and suitable underground routes. Burial design includes bedding preparation, ground conditions, safe pulling and the specified minimum bending radius.

Sheath selection follows the route: standard PVC, low-smoke halogen-free compounds and materials for chemical or prolonged water exposure have different properties and test requirements.

Glands match the armour dimensions and overall cable diameter. Where armour serves as a protective conductor, fault-current capacity and electrical continuity are assessed for the complete connection. See the MV steel wire armour construction guide for details.

Find the Matching Cable Range

Project requirementRelated XWA rangeRelationship to this structure family
Fixed low-voltage power circuitsNiederspannungskabelVoltage-class context; includes constructions other than SWA
Screened distribution feedersMittelspannungskabelScreened electrical designs; armour is specified separately
Transmission-system requirementsHochspannungskabelFull electrical, sheath and accessory system definition
An aluminium phase conductorAluminium CableConductor-material range; aluminium conductor does not mean aluminium armour

Erkunden Kabeltypen und -modelle for related voltage classes, named cable models and conductor families.

Project Lengths and Factory Support

XWA supports power cable manufacturing to customer drawings and cable schedules. The agreed construction defines the electrical specification, while quantities and drum lengths set the delivery arrangement.

For the proposed design, the technical submission should identify the cable drawing, Dimensionsdaten, agreed tests and drum information. Outside diameter and finished cable mass affect drum selection, lifting and pulling equipment. Drum tare is additional to cable mass; the agreed minimum bending diameter must also fit the drum barrel.

Große Stahlkabeltrommeln mit aufgewickeltem schwarzem Kabel in einer Fabrikhalle
Stahlspulen mit aufgewickeltem Kabel für Handhabung und Trommelplanung.

To discuss a project with XWA, use the existing enquiry form or contact info@xwacable.com / WhatsApp. Manufacturing scope, inspection documents and delivery arrangements are confirmed against the requested construction.

XLPE/SWA/PVC Cable Questions

What does XLPE/SWA/PVC mean?

XLPE identifies the insulation, SWA the steel wire armour and PVC the outer sheath. Leitermaterial, Kernzahl, rated voltage and any electrical screens complete the specification.

Is XLPE/SWA/PVC cable only low voltage?

The construction is used in LV and screened MV designs. Higher-voltage armoured cables use a dedicated cable-system design, including voltage-appropriate insulation, screens and sheath arrangements.

Can a single-core AC cable use ordinary steel wire armour?

Ordinary ferromagnetic steel armour around a single AC phase can increase losses and heating. Non-magnetic armour such as AWA is commonly used; special steel arrangements require a loss and bonding assessment.

Does SWA make a cable waterproof or fire resistant?

SWA provides mechanical protection. Waterproofing, fire behaviour and continued circuit operation during fire each require the relevant materials, construction and tests.

    Holen Sie sich ein kostenloses Angebot ein 24 Std

    E-Mail*:

    Name*:

    Dein Land:

    Tel.*:

    Ihre Anforderungen*: