SHD-GC Madencilik Kablosu

XWA Gücü & Kablo | Kauçuk Kablo Modelleri

SHD-GC for shielded trailing power for mobile mining plant

Voltage class shown: 5 kV AC (5,000 V)

SHD-GC cable is a shielded mining trailing cable with flexible power cores, grounding conductors and a ground-check conductor. Its screened power-core construction suits equipment connections where voltage control and ground monitoring must work together.

The reference design on this page is a three-power-core, 5 kV inşaat. Each phase includes the appropriate conductor screen, EPR insulation and flexible metallic shielding arrangement. Different SHD-GC voltage classes have different insulation and dimensional schedules.

SHD-GC mining cable sample with exposed copper conductors and a black outer sheath
SHD-GC mining cable sample.

5 kV referans yapısı

SHD-GC conductor and layer arrangement

5 kV korumalı örnek kesit gösterimi 3 ekranlanmış güç çekirdekleri, 2 topraklama iletkenleri, 1 yalıtımlı kontrol çekirdeği, Güçlendirilmiş ceket
SHD-GC construction schematic.
BileşenYapı
Faz iletkeniThree flexible rope-lay copper conductors.
Conductor screen and insulationSemiconductive conductor screen followed by EPR insulation.
Insulation shieldingFlexible copper/textile braid shielding around each insulated phase in the reference design.
Grounding and checkTwo grounding conductors plus a separately insulated ground-check core.
Dış korumaReinforced heavy-duty jacket enclosing the complete assembly.

ICEA S-75-381 / TUVALET YOK 58 provides the mining-cable construction and test framework. The cited dimensional group is specifically 5 kV, 100% yalıtım seviyesi, grounded service. Other voltage groups require their own design tables.

SHD-GC reference sizes and technical data

Elektrik parametresiŞartname
Nominal gerilim5 kV AC (5,000 V)
Derecelendirme kuralıSeçildi 5 kV inşaat; 100% yalıtım seviyesi, grounded service
İnşaat standardı referansıICEA S-75-381 / TUVALET YOK 58
Çekirdek düzenlemesiThree screened power cores, two grounding conductors and one ground-check conductor.
Güç çekirdekleriZemin (AWG)Check (AWG)Yalıtım (mm)Ceket (mm)İLE İLGİLİ (mm)Yığın (kg/km)Akım (A)
3 × 1/0 AWG482.85.652.34530211
3 × 2/0 AWG382.85.655.15315243
3 × 4/0 AWG182.86.068.87380321

Seçildi 5 kV referans yapısı: three power cores, iki topraklama iletkeni ve bir kontrol çekirdeği; 100% yalıtım seviyesi, grounded. Reference current values use 90°C conductor and 40°C ambient air under ICEA S-75-381/NEMA WC 58; reel layers and installation conditions require correction.

Shield termination belongs in the machine connection design

Power shovels, draglines and other relocatable mining plant place combined electrical and mechanical demands on their supply cable. The power-core shields, topraklama iletkenleri, monitor loop and coupler must remain coordinated when cable is extended, repaired or replaced.

We would treat the coupling arrangement as part of the cable requirement from the outset. A heavier jacket can improve mechanical protection, but it does not address a mismatched shield connection or an unsuitable ground-check termination.

SHD-GC and related rubber cable types

Kablo ailesiİlgili ayrım
Tip G-GCGround-check cable with a different power-core screening arrangement; the selected reference is 2 kV.
SHD-GC 5 kVScreened power cores and monitoring conductors for the defined 5 kV duty.
SHD-GC at other voltagesSeparate insulation, ekran, diameter and coupling requirements; retain the exact voltage class.

For the wider context of SHD-GC applications, keşfetmek kauçuk kablo aralığı, NSSHÖU ağır hizmet kablosu ve bizim XWA fabrika bilgileri.

SHD-GC cable questions

What distinguishes SHD-GC from G-GC?

SHD-GC adds a shielded power-core construction. Both the shield system and the required voltage class affect dimensions, grounding and termination design.

bir 5 kV table apply to 8 kV veya 15 kV kablosu?

HAYIR. Each voltage class requires the corresponding insulation and screen design. The reference dimensions on this page describe only the stated 5 kV inşaat.

Is the ground-check conductor the same as a grounding conductor?

The check core is used in the monitoring loop. The grounding conductors and the shield-grounding arrangement carry their specified protective duties.