XLPE/SWA/LSZH কেবল

এইচডব্লিউএ পাওয়ার & CABLE | ARMOURED HALOGEN-FREE CONSTRUCTIONS

XLPE/SWA/LSZH কেবল combines cross-linked polyethylene insulation, steel wire armour and a low-smoke zero-halogen outer sheath. It is a construction family for fixed power routes where mechanical protection and specified smoke and gas performance are both important.

In enclosed power routes, smoke and combustion gases deserve attention alongside mechanical protection. Our recommendation is to treat the insulation, fillers, bedding and sheath as one material system, with the required smoke, gas and flame tests specified together. Rated voltage and metallic screens then define the electrical construction for the circuit.

Discuss an LSZH armoured cable project
নিরোধক
এক্সএলপিই
Mechanical layer
ইস্পাত তারের বর্ম
বাইরের খাপ
Low smoke, zero halogen

XLPE/SWA/LSZH layer combinations

An unscreened construction is CU/XLPE/LSZH/SWA/LSZH: copper conductor, XLPE নিরোধক, halogen-free bedding, wire armour and halogen-free sheath. Whole-cable smoke and halogen performance depends on the bedding, fillers and other non-metallic components as well as the outer sheath.

Unscreened distribution construction

Multicore LV designs combine the insulated core assembly with bedding, SWA and an outer sheath. Equal-section cores, reduced neutrals and protective cores are separate circuit arrangements; conductor material and core count remain part of the specification.

Screened MV construction

A screened MV example is CU/XLPE/CTS/LSZH/SWA/LSZH. Semiconductive layers control the electric field, the copper tape screen performs the specified electrical duty, and steel wire armour protects the assembly mechanically. Copper-wire screening is another option.

Cut end of a four-core copper cable showing coloured core insulation and a ring of armour wires
Four-core cable cross-section with copper conductors and steel wire armour.

Screened three-core cable construction

Three-core XLPE/SWA/LSZH cable illustration showing copper conductors, অন্তরণ, ধাতব পর্দা, inner bedding, steel wire armour and outer sheath
Screened three-core XLPE/SWA/LSZH construction. Illustration – not to scale.
ElementWhat it contributesWhat the short name leaves open
Copper or aluminium conductorCarries circuit currentউপাদান, ক্লাস, shape, section and neutral/earth arrangement.
XLPE নিরোধকSeparates conductors electricallyরেটেড ভোল্টেজ, insulation thickness and any field-control layers.
Fillers and beddingSupports the laid-up cores and armourCompound, tape system and their contribution to declared fire properties.
ইস্পাত তারের বর্মMechanical protection around a multicore assemblyWire dimensions, corrosion protection and bonding/protective-conductor assessment.
LSZH outer sheathSpecified smoke and halogen-related performanceCompound grade, fire tests, weather resistance and environmental limits.

SWA is commonly used around multicore AC assemblies. Single-core AC circuits generally use non-magnetic armour, such as aluminium wire armour, to control magnetic losses and heating.

Low-smoke materials and fire-performance requirements

For enclosed power routes, the useful question is how the complete cable performs in the specified fire tests. Smoke emission, combustion gases and flame spread describe different aspects of that performance; the table separates them so each requirement can be matched to the project.

PropertyRelevant test frameworkMeaning for a project
Smoke emissionআইইসি 61034-2Measures smoke emission under defined cable-burning conditions against the specified requirement.
Halogen acid gasআইইসি 60754-1Tests gases from cable materials against the specified requirements.
Acidity and conductivityআইইসি 60754-2Assesses gas-related acidity/conductivity; separate from optical smoke measurement.
Flame spreadApplicable IEC 60332 পরীক্ষাSingle-cable and bunched-cable tests are different scopes.
Circuit integrity in fireApplicable fire-resistance specificationRequires a fire-resistant construction qualified for the specified circuit-integrity test.

দ official smoke-test procedure explains how smoke emission is measured under IEC 61034-2. The project specification sets the required smoke, gas and flame-spread performance; circuit integrity during fire is a separate tested requirement.

Voltage and screens define each power-cable design

Construction scopeLayer distinctionTechnical information carried by its datasheet
LV armoured power cableXLPE-insulated core assembly, halogen-free bedding, SWA and LSZH sheathভোল্টেজ, core functions, conductor class and shape, মাত্রা, installation limits and fire declarations.
MV screened armoured power cableAdditional semiconductive layers and metallic screening matched to the voltageScreen construction and fault duty, নিরোধক সিস্টেম, আনুষাঙ্গিক, bonding and project installation rating.
Higher-voltage project requestA complete cable-system design, not an LV construction scaled upApplicable system standard, metallic sheath/screen, ক্ষতি, বন্ধন, accessories and qualification evidence.

The dimensions below cover a four-core 0.6/1 kV construction. Medium-voltage cable systems use additional electrical screens and voltage-specific insulation, with their own dimensions and accessories. Higher-voltage systems require a dedicated cable-system design.

Large-section reference: four-core copper, 0.6/1 কেভি

প্রস্তাবিত রেফারেন্স ডেটা: four equal-section class 2 copper cores, XLPE নিরোধক, LSZH bedding, SWA and LSZH sheath. These published reference dimensions support preliminary planning; final supply dimensions follow the agreed XWA datasheet.

Cores × section (মিমি²)সর্বোচ্চ. 20 ডিগ্রি সেলসিয়াসে ডিসি প্রতিরোধের (Ω/কিমি)নিরোধক (মিমি)বাইরের খাপ (মিমি)সামগ্রিক ব্যাস (মিমি)প্রায়. ভর (কেজি/কিমি)
4 × 500.3871.02.134.53400
4 × 700.2681.12.239.64727
4 × 950.1931.12.444.06567
4 × 1200.1531.22.649.97748
4 × 1500.1241.42.754.39609
4 × 2400.07541.73.166.114496

Insulation and sheath thicknesses are nominal in this reference. Other conductor shapes, bedding compounds and armour dimensions produce different overall diameters and weights even at the same nominal section. Three-core, five-core and reduced-neutral designs need their own rows.

Current rating is calculated for the installation method, loaded cores, পরিবেষ্টিত তাপমাত্রা, grouping and soil conditions. The project datasheet and route calculation establish the circuit rating.

Finished diameter determines gland entry and termination space. Bedding, sheath and armour dimensions also affect mass and bending behaviour, so accessory selection follows the finished cable dimensions.

Mechanical protection on routes with smoke and gas requirements

In plant rooms, transport infrastructure and occupied industrial buildings, a power route can need both physical protection and controlled smoke and combustion-gas performance. XLPE/SWA/LSZH brings those requirements into one fixed cable construction: wire armour serves the mechanical duty, while the selected non-metallic materials address the specified fire tests.

Where the same feeder passes from an enclosed building to an outdoor route, sheath selection also needs to address weather, moisture and any chemical exposure. A useful design balances those route conditions with the required fire performance, rather than treating LSZH as a complete environmental specification.

For wet fixed routes, dedicated water-blocking layers can be specified alongside the armour. Installation temperature and bending requirements remain part of the finished cable specification.

XWA cable manufacturing and project supply

এক্সডব্লিউএ পাওয়ার & Cable manufactures power cables in Henan, চীন. Conductor processing, insulation extrusion, armouring and sheathing are part of our cable factory operations.

XWA supports cable manufacturing to project drawings and cable schedules. The agreed LSZH design brings together the electrical rating, non-metallic materials and specified smoke, halogen and flame tests.

Delivery length is part of the configuration. The finished diameter and mass establish a starting point for drum dimensions, handling equipment and route pulling arrangements; gross drum weight includes more than cable conductor weight.

Large steel cable reels with wound black cable on a factory floor
Steel reels with wound cable for handling and drum planning.

Questions about the LSZH armoured structure

What does XLPE/SWA/LSZH mean?

XLPE identifies the insulation, SWA the steel wire armour and LSZH the low-smoke zero-halogen outer-sheath family. কন্ডাক্টর, বিছানাপত্র, পর্দা, voltage and test requirements complete the specification.

Is CU/XLPE/LSZH/SWA/LSZH a separate model name?

It describes the layers from the centre outwards: copper conductor, XLPE নিরোধক, LSZH bedding, steel wire armour and LSZH outer sheath.

Can this structure be used for medium voltage?

হ্যাঁ. Screened MV constructions combine XLPE insulation, voltage-appropriate semiconductive layers, a metallic screen, armour and an LSZH sheath system. Screen fault duty, dimensions and accessories are selected for the voltage rating.

Does an LSZH outer sheath make PVC bedding halogen-free?

PVC bedding contains halogen. A whole-cable halogen-free specification addresses the fillers, বিছানাপত্র, tapes and sheath together, with the corresponding material and test requirements.

Is XLPE/SWA/LSZH cable fire-resistant?

LSZH describes smoke and halogen-related properties. Continued circuit operation during fire requires a fire-resistant construction and a corresponding circuit-integrity test.

Can steel wire armour replace a copper screen?

Steel wire armour provides mechanical protection; a copper screen performs the specified electrical duty. A screened MV armoured cable contains both layers.

Request an XLPE/SWA/LSZH cable quotation

Discuss your LSZH cable requirement with XWA. Email a cable schedule, or tell us the voltage, core size and length, together with any specified fire-performance requirements.