NA2XS(চ)2এবং তারের

NA2XS(চ)2এবং তারের is a single-core medium-voltage power cable with a stranded aluminium conductor, screened XLPE insulation, copper wire screen and black PE outer sheath. দ (চ) construction includes longitudinal water-blocking components in the screen area.

Fixed distribution feeders, substations and industrial power routes use this cable type where the installation design calls for an aluminium conductor and a water-blocked screened core. কন্ডাক্টরের আকার, পর্দা এলাকা, voltage and route conditions define the final configuration.

Aluminium single-core XLPE cable cutaway showing the conductor, copper wire screen and black PE sheath
Single-core aluminium construction with metallic screening. Illustration, not to scale.

নির্মাণ

কন্ডাক্টর
Stranded aluminium, ক্লাস 2
নিরোধক
XLPE with inner and outer semiconductive screens
ধাতব পর্দা
Copper wires with cross-connection tape; swellable components
বাইরের খাপ
Black polyethylene; unarmoured reference design

বৈশিষ্ট্য

Reference voltage
12/20 (24) কেভি
Water blocking
Longitudinal water blocking in the screen region; no separate radial moisture barrier
ইনস্টলেশন
Fixed underground, duct and industrial feeder routes
Standard context
DIN VDE 0276-620 / এইচডি 620; project-specific IEC requirements

NA2XS(চ)2Y for Fixed Power Distribution

ভোল্টেজ, conductor/screen size and route conditions define the project configuration.

একটি উদ্ধৃতি অনুরোধ

NA2XS(চ)2Y কেবল প্রযুক্তিগত ডেটা

Recommended reference data. Final dimensions and ratings follow the approved project configuration; the selected rows are not a confirmed XWA production range.

তারের আকার
(মিমি²)
ডিসি প্রতিরোধ
20°সে (Ω/কিমি)
নিরোধক
(মিমি)
প্রায়. অফ
(মিমি)
প্রায়. ভর
(কেজি/কিমি)
Air
(ক)
Ground
(ক)
1 x 95/160.3205.532991280251
1 x 150/250.2065.5351284366319
1 x 240/250.1255.5391661496417
1 x 300/250.1005.5411871569471
1 x 400/350.07785.5442324660535
1 x 630/350.04695.5513202883705

Single-core aluminium/XLPE/copper-wire-screen/PE, 12/20(24) কেভি. The second area in 1×240/25 identifies the metallic screen, not another phase conductor.

Reference ampacity: one circuit, touching trefoil; air 30°C; ground 20°C, thermal resistivity 1.0 K·m/W and burial depth 0.7 মি. Reference maximum conductor temperature: 90°সে. নালী, grouped circuits and bonding require a project calculation.

Longitudinal water blocking and three single-core circuits

Swellable components limit water movement along the cable after moisture enters. They do not repair sheath damage or establish a separate radial moisture barrier. Water-blocked conductors, radial barriers and immersion conditions require their own construction and evidence.

স্বরলিপি 3×1×240 describes three individually sheathed single-core cables, each with a 240 mm² conductor. It is not a three-core assembly. Drum allocation, ক্লিটস, cable entries and screen connections follow that distinction.

Diagram distinguishing water movement along a cable from radial entry through its sheath
Longitudinal blocking and a radial barrier address different moisture paths.
Three separate single-core aluminium cable cross-sections explaining the notation 3 x 1 x 240
Three single-core cables remain three individually sheathed products, even when installed together.

Applications and Installation Conditions

Utility distribution, transformer-substation connections and industrial feeders are typical fixed-installation contexts. যান্ত্রিক সুরক্ষা, তাপ নকশা, end sealing and aluminium-compatible connections remain part of the cable system. Ordinary PE sheath is not a substitute for a specified flame-retardant or LSZH design.

প্রতিরোধ, partial-discharge and voltage-test records do not replace evidence for longitudinal water penetration or sheath integrity. The declared water-blocking construction and its test scope must agree. The official IEC scope provides standard context, not a VDE certificate or utility approval.

NA2XS(চ)2Y and Related Constructions

মডেলMain difference
NA2XSY cableAluminium conductor and PVC outer sheath instead of PE; longitudinal water blocking is not specified by the NA2XSY designation.
N2XS2Y cableCopper conductor instead of aluminium, with XLPE insulation and a PE sheath; longitudinal water blocking is not specified by the N2XS2Y designation.
NA2XS(FL)2YAdds a laminated metallic moisture barrier beneath the PE sheath, providing radial moisture protection in addition to longitudinal water blocking.

NA2XS(চ)2Y কেবল FAQs

কি করে (চ) mean in NA2XS(চ)2Y?

It identifies longitudinal water blocking. The exact tape arrangement and tested scope follow the declared construction; it does not by itself specify a radial barrier or a water-blocked conductor.

Does an aluminium conductor mean an aluminium screen?

না. The reference uses an aluminium phase conductor and a copper wire metallic screen. Screen area follows earth-fault duty and bonding requirements.

Is 3×1×240 the same as a three-core cable?

না. It is three separate single-core cables. A three-core cable contains the three phase cores inside one common sheath.