Dry type transformers use solid insulation and air cooling rather than an oil-filled tank. XWA offers cast-resin transformer configurations for building substations, industrial distribution and project power systems where equipment location, ventilation and service access shape the design.

The SC(B) cast-resin family combines resin-insulated windings with an air-cooled assembly. Të 10/10.5 kV në 0.4 kV series presented here covers 30 te 2,500 kVA. The product programme also includes separate 35 kV cast-resin designs.

XWA works with a specialist transformer manufacturing partner to coordinate product selection, technical schedules and quotations for international projects. Send your required rating and voltage ratio to start a transformer enquiry.

Three-phase dry type transformer with red cast-resin coils and a blue support frame
Three-phase cast-resin dry type transformer.

Cast-resin windings and a clear airflow path

The cast-resin construction encapsulates the winding insulation system and leaves air passages around the active assembly. This arrangement suits indoor electrical rooms where an oil containment system would add installation complexity.

Cooling and enclosure work together

Natural-air cooling relies on free air movement through the winding assembly. Fan-assisted cooling is a separately specified operating condition, with its own permissible output and control arrangement. An enclosure changes the airflow path, so its protection rating and ventilation openings belong in the same thermal assessment.

Our recommendation for an indoor project is to settle the room arrangement early: intake and exhaust locations, zhdoganimet, ambient temperature and service access affect the installation as much as the transformer footprint.

Schematic of cool air entering below cast-resin windings and warm air leaving above
Airflow around cast-resin windings.

SC(B)18 cast-resin technical data

ParametriConfiguration
Product familySC(B)18 cast-resin, trefazore
Capacity series30–2,500 kVA at the stated voltage combination
Primary / secondary10 ose 10.5 kV / 0.4 kV
Vector group optionsDyn11 or Yyn0, selected for the system
HV tapping options±2 × 2.5% or ±5%, siç specifikohet
Frequency and cooling ratingProject-specific frequency; natural-air or fan-assisted configuration
Thermal system and enclosureInsulation class, winding temperature rise and enclosure selected together

Selected SC(B)18 ratings: 10/0.4 kV

Rated capacity (kVA)No-load loss (W)Short-circuit impedance (%)
1002304.0
2504154.0
5006704.0
8008754.5
1,0001,0204.5
1,6001,4154.5
2,5002,0805.0

Catalogue values for the stated product family and voltage ratio. Dimensionet përfundimtare, load losses at the specified reference temperature and guaranteed performance are recorded in the project datasheet.

Në 0.4 kV, a three-phase 1,000 kVA transformer has a rated line current of approximately 1,443 A, calculated as 1,000,000 / (√3 × 400). Switchgear connections, terminals and busbar arrangements therefore need to be considered alongside the kVA rating.

Compare losses at the same rating

For the 1,000 kVA, 10/0.4 kV configurations below, catalogue no-load losses are 1,415 W for SC(B)12, 1,205 W for SC(B)14 dhe 1,020 W for SC(B)18. The comparison isolates core losses; winding losses and the actual load profile determine the rest of the operating loss.

A lower core-loss value is particularly useful when a transformer remains energised for long periods at modest load. At high loading, the winding-loss schedule becomes more influential. Comparing both at the agreed reference conditions gives a more useful picture than an isolated efficiency percentage.

Temperature class is part of the thermal design

Class F and Class H identify insulation-system thermal classes. The permitted winding temperature rise, kushtet e ambientit, cooling mode and enclosure remain separate design inputs. Temperature sensing and fan control, where fitted, should be coordinated with the selected rating and protection settings.

1000 kVA dry transformer no-load loss chart: SC(B)12 1415 W, SC(B)14 1205 W, SC(B)18 1020 W
No-load losses for three 1,000 kVA cast-resin configurations.

Where cast-resin transformers fit

Project settingDesign focus
Commercial and public buildingsIndoor distribution rooms, rising-main supply and accessible maintenance routes.
Objektet industrialeProcess-load distribution with attention to motor starting, harmonics and expansion duty.
Urban substationsElectrical-room layouts with ventilation and acoustic requirements established.
Renewable-energy auxiliariesSite distribution duties matched to the voltage ratio and load characteristics.

For an indoor room with restricted ventilation, the enclosure and air path deserve attention before the footprint is fixed. For an outdoor installation, an oil-immersed alternative may offer a different balance of cooling, space and site works. Eksploroni XWA power transformer range for the wider programme.

Standards and project inspection

IEC 60076-11 addresses dry-type power transformers within its defined scope. IEC 60076-1 covers general requirements and IEC 60076-3 addresses winding insulation and dielectric tests.

The specification establishes applicable standards and editions, testet, reference temperatures, acceptance values and inspection responsibilities. Winding resistance, raporti i tensionit, phase displacement, losses and dielectric performance are key items in a transformer test schedule; temperature-rise and additional tests follow the contract requirements.

Technical review aligns the electrical schedule with the installation drawing: terminal arrangement, lifting points, dimensionet, earthing provisions and transport configuration. This makes documentation useful to the installation team as well as the project reviewer.

Referenca: IEC dry-type transformer standard scope.

Dry Type Transformer FAQs

Is a cast-resin transformer a dry type transformer?

po. Cast resin is a dry-type construction in which resin forms part of the winding insulation system. Other dry-type constructions use different insulation processes.

Can a dry type transformer be installed outdoors?

An outdoor installation needs a suitable enclosure, weather protection, ventilation and environmental design. The complete assembly and site conditions determine suitability.

Which voltage and capacity does this range cover?

The detailed SC(B)18 examples on this page cover the 10/10.5 kV në 0.4 kV, 30–2,500 kVA family. Separate technical schedules apply to 35 kV designs and other voltage ratios.

What starts a project quotation?

The required kVA rating, primary and secondary voltages, frekuenca, quantity and installation location start the discussion. A single-line diagram or transformer schedule helps align the remaining details.