N2XSEY cable is a three-core medium-voltage power cable with stranded copper conductors, screened XLPE insulation and a common PVC outer sheath. Three phase cores form one assembled cable for fixed distribution.

The reference CU/XLPE/CTS/PVC construction uses metallic screening but no armour. The shared sheath distinguishes it from a circuit of three separate single-core cables and changes handling mass, cable-entry dimensions and installation geometry.

Concept illustration of three individually screened copper cores within a common PVC cable sheath
Three screened copper cores inside one PVC sheath. Ilustrimi i konceptit, not to scale.

NDËRTIMI

Conductors
Three stranded copper phase conductors
Insulated cores
Semiconductive screens and XLPE insulation
Ekrane metalike
Copper tape screening in the reference construction
Assembly
Filler and common PVC sheath; unarmoured

KARAKTERISTIKAT

Reference voltage
12/20 kV for the displayed dataset
Core layout
Three screened cores in one cable body
Thermal reference
90°C maximum operating conductor temperature in the source design
Standard context
IEC 60502-2 and relevant VDE/HD project requirements

N2XSEY for Fixed Power Distribution

Tensioni, conductor/screen size and route conditions define the project configuration.

Kërkoni një kuotë

N2XSEY Cable Technical Data

Të dhënat referuese të rekomanduara: published values for preliminary comparison. Final supply dimensions, ratings and size range follow the agreed XWA datasheet.

Madhësia e kabllit
(mm²)
DC resistance
20°C (Ω/km)
Përafërsisht. OD
(mm)
Përafërsisht. masë
(kg/km)
Air
(A)
Ground
(A)
3 x 95/160.193067.06900326316
3 x 150/250.124074.59250426404
3 x 185/250.099178.510650488457
3 x 240/250.075485.013000576532
3 x 300/250.060190.015250654599
3 x 400/350.047098.019100750685

Three-core CU/XLPE/CTS/PVC, 12/20 kV. Diameter and mass refer to the assembled cable; the slash notation identifies the separately specified metallic-screen section.

Reference ampacity: one system; air 30°C, faktori i ngarkesës 1.0; ground 20°C, thellësia 0.7 m, rezistenca termike 1.0 K·m/W, faktori i ngarkesës 0.7. Reference conductor limit: 90°C. Continuous full-load burial requires a rating calculated at load factor 1.0.

Three-core construction and accessory interfaces

N2XSEY assembles the three phase cores within a common sheath. Separate single-core cables permit flat or trefoil formation; each arrangement has its own current-rating, handling and support requirements.

Termination stress-control components fit the insulation diameter and screen treatment. Glands and entry seals fit the complete cable diameter. The 3×240/25 reference is approximately 85 mm in diameter and 13 kg/m, before drum tare; handling calculations therefore use assembly mass, not copper mass alone.

Schematic of three individually screened copper cores, Izolimi XLPE, filler and common PVC sheath
Three screened cores share one outer sheath; the drawing is explanatory and not to scale.
Diagram separating cable voltage designation from insulation diameter and overall diameter for accessory fit
Termination, joint and gland selection follows the insulation diameter, screen arrangement and finished cable diameter.

Applications and Installation Conditions

Industrial distribution, substation connections and suitable underground or ducted feeders can use this combined three-core assembly. Diametri i kabllit, mass and bending limits inform route access and pulling equipment. Routes requiring armour, water blocking or enhanced fire performance use the corresponding construction.

The manufacturing specification defines screens, insulation and sheath thicknesses, accessory dimensions and tests for the three-core assembly. The official standard scope describes the fixed-distribution cable framework.

N2XSEY and Related Constructions

ModelMain difference
N2XSY single-core cableEach phase cable has its own sheath; circuit geometry and bonding need separate assessment.
20 Gama e kabllove kVVoltage-class context for 12/20(24) kV projects, rather than an exact three-core model.
Armoured MV constructionMechanical armour adds a separate layer and changes the specified design and dimensions.

N2XSEY Cable FAQs

Does N2XSEY mean the cable is armoured?

The reference N2XSEY construction is screened and unarmoured. Its metallic screen performs an electrical duty; mechanically protected variants add a separate armour layer.

Can 12/20 kV dimensions be used for a 6/10 kV variant?

The table covers the stated 12/20 konstruksion kV. A 6/10 kV version uses its own insulation dimensions and construction-specific rating data.

Is N2XSEY the same as three N2XSY cables?

N2XSEY combines three phase cores inside a common sheath. Three N2XSY cables are separately sheathed single-core products, with different handling and installation arrangements.