Газрын тосны трансформаторууд use insulating oil to provide electrical insulation and transfer heat from the active part to the tank cooling surfaces. XWA offers sealed distribution and higher-voltage oil-filled configurations for utility networks, industrial sites and project substations.
The S-M sealed distribution family includes 10/10.5 кВ хүртэл 0.4 kV configurations from 30 руу 2,500 kVA. Separate 35 kV two-winding designs cover distribution and industrial substation duties, with their own winding, insulation and impedance schedules.
XWA works with a specialist transformer manufacturing partner to coordinate product selection, technical schedules and quotations for international projects. Send your required rating and voltage ratio to start a transformer enquiry.

A sealed tank with oil-to-air cooling
The windings and magnetic core sit within the insulating-oil system. Heat passes to the oil, then through the tank walls, corrugations or radiators to the surrounding air. The external cooling arrangement is matched to the transformer rating and installation conditions.
Sealed distribution and conservator designs
A sealed corrugated-tank distribution design accommodates oil-volume changes through its tank arrangement. Larger or different-duty units may use radiators and a conservator. Tank construction, oil preservation and accessories follow the selected transformer design rather than one universal enclosure layout.
ONAN describes oil-natural, air-natural cooling. Other cooling arrangements use a different combination of circulation and airflow. We recommend reviewing cooling duty alongside ambient temperature and the loading cycle, especially for an enclosed or hot-climate site.

S20-M oil-immersed distribution technical data
| Параметр | Тохиргоо |
|---|---|
| Бүтээгдэхүүний гэр бүл | S20-M sealed, three-phase oil-immersed |
| Capacity series | 30–2,500 kVA at the stated voltage combination |
| Primary / secondary | 10 эсвэл 10.5 кВ / 0.4 кВ |
| Insulating medium | Mineral oil in the illustrated S-M family |
| Vector group options | Dyn11 or Yyn0, selected for the system |
| HV tapping options | ±2 × 2.5% or ±5%, as specified |
| Frequency and cooling duty | Project frequency and cooling designation stated in the agreed technical schedule |
Selected S20-M ratings: 10/0.4 кВ
| Rated capacity (kVA) | No-load loss (W) | Short-circuit impedance (%) |
|---|---|---|
| 100 | 135 | 4.0 |
| 250 | 260 | 4.0 |
| 500 | 430 | 4.0 |
| 800 | 630 | 4.5 |
| 1,000 | 745 | 4.5 |
| 1,600 | 1,050 | 4.5 |
| 2,500 | 1,440 | 5.0 |
Catalogue values for the stated product family and voltage ratio. Final dimensions, load losses at the specified reference temperature and guaranteed performance are recorded in the project datasheet.
At 0.4 кВ, a three-phase 1,000 kVA transformer has a rated line current of approximately 1,443 А, calculated as 1,000,000 / (√3 × 400). Switchgear connections, terminals and busbar arrangements therefore need to be considered alongside the kVA rating.
Core loss matters throughout energised operation
For the 1,000 kVA, 10/0.4 kV examples below, catalogue no-load losses are 830 W for S13-M, 745 W for S20-M and 665 W for S22-M. These are three product configurations at the same rating, not three measurements of one unit.
No-load loss continues while a transformer is energised. Load loss varies with loading and winding temperature. For a substation with long lightly loaded periods, core-loss reduction can matter more than a comparison based only on full-load operation. A heavily loaded industrial feeder needs a closer look at both loss components.
Voltage ratio, taps and parallel operation
Taps adjust the effective turns ratio within the selected range. De-energised tap changing and on-load tap changing use different equipment and operating procedures. For parallel operation, ratio, vector group, impedance and tap position must be coordinated so load sharing and circulating currents remain within the intended design.

Oil-immersed transformer applications
| Project setting | Design focus |
|---|---|
| Utility distribution | Outdoor medium-voltage to low-voltage supply for local networks. |
| Industrial substations | Dedicated plant supply with ratio, protection and impedance matched to the network. |
| Project infrastructure | Distribution for developments, commercial sites and public infrastructure. |
| 35 kV user substations | Separate two-winding designs for higher-voltage distribution and industrial supply. |
For outdoor distribution, the tank and cooling surfaces form a practical self-contained assembly. For an indoor room, a cast-resin alternative may simplify the installation where fire strategy or oil containment is a deciding factor. -г судлах XWA power transformer range for the wider programme.
Standards and project inspection
IEC 60076-1 covers general power-transformer requirements. IEC 60076-2 addresses liquid-immersed transformer temperature rise and cooling identification; IEC 60076-3 covers insulation levels and dielectric tests.
The specification establishes applicable standards and editions, туршилтууд, reference temperatures, acceptance values and inspection responsibilities. Winding resistance, хүчдэлийн харьцаа, phase displacement, losses and dielectric performance are key items in a transformer test schedule; temperature-rise and additional tests follow the contract requirements.
Technical review aligns the electrical schedule with the installation drawing: terminal arrangement, lifting points, хэмжээсүүд, earthing provisions and transport configuration. This makes documentation useful to the installation team as well as the project reviewer.
Лавлагаа: IEC liquid-immersed cooling and temperature-rise scope.
Oil-Immersed Transformer FAQs
What is the difference between oil-filled and oil-immersed transformers?
In this product context both commonly describe a transformer whose active part uses an insulating-oil system. The tank, cooling arrangement, voltage and winding design identify the particular product.
What does ONAN mean?
ONAN means oil natural, air natural: natural oil circulation transfers heat to cooling surfaces, while natural airflow carries it away. The complete rating also depends on thermal and site conditions.
Is 10 kV the same transformer rating as 11 кВ?
They are separate ratings. Turns ratio, insulation and taps are selected for the actual system voltage; an 11 kV enquiry requires its own matching technical schedule.
What information is needed for a quotation?
Send kVA or MVA rating, хүчдэлийн харьцаа, давтамж, quantity and destination. A single-line diagram and utility specification help define winding connections, impedance, taps, accessories and inspection requirements.
Discuss your transformer requirement with XWA
Send capacity, primary and secondary voltages, давтамж, quantity and project destination. Include a single-line diagram or transformer schedule if available. XWA can coordinate the configuration and quotation with our transformer manufacturing partner.