NA2XS(Ф)2и кабель

NA2XS(Ф)2и кабель представляет собой одножильный силовой кабель среднего напряжения с многопроволочной алюминиевой жилой., screened XLPE insulation, copper wire screen and black PE outer sheath. The (Ф) construction includes longitudinal water-blocking components in the screen area.

Fixed distribution feeders, substations and industrial power routes use this cable type where the installation design calls for an aluminium conductor and a water-blocked screened core. Размер проводника, область экрана, voltage and route conditions define the final configuration.

Aluminium single-core XLPE cable cutaway showing the conductor, copper wire screen and black PE sheath
Single-core aluminium construction with metallic screening. Illustration, not to scale.

СТРОИТЕЛЬСТВО

Дирижер
Многожильный алюминий, Сорт 2
Изоляция
XLPE with inner and outer semiconductive screens
Металлический экран
Copper wires with cross-connection tape; swellable components
Внешняя оболочка
Black polyethylene; unarmoured reference design

ХАРАКТЕРИСТИКИ

Reference voltage
12/20 (24) кВ
Water blocking
Longitudinal water blocking in the screen region; no separate radial moisture barrier
Установка
Fixed underground, duct and industrial feeder routes
Standard context
DIN VDE 0276-620 / HD 620; project-specific IEC requirements

NA2XS(Ф)2Y for Fixed Power Distribution

Напряжение, conductor/screen size and route conditions define the project configuration.

Запросить ценовое предложение

NA2XS(Ф)2Технические данные Y-кабеля

Рекомендуемые справочные данные. Final dimensions and ratings follow the approved project configuration; the selected rows are not a confirmed XWA production range.

Размер кабеля
(мм²)
сопротивление постоянному току
20°С (Ом/км)
Изоляция
(мм)
Приблизительно. ИЗ
(мм)
Приблизительно. масса
(кг/км)
Воздух
(А)
Земля
(А)
1 х 95/160.3205.532991280251
1 х 150/250.2065.5351284366319
1 х 240/250.1255.5391661496417
1 х 300/250.1005.5411871569471
1 х 400/350.07785.5442324660535
1 х 630/350.04695.5513202883705

Single-core aluminium/XLPE/copper-wire-screen/PE, 12/20(24) кВ. The second area in 1×240/25 identifies the metallic screen, not another phase conductor.

Reference ampacity: одна цепь, трогательный трилистник; air 30°C; ground 20°C, термическое сопротивление 1.0 K·m/W and burial depth 0.7 м. Reference maximum conductor temperature: 90°С. воздуховоды, grouped circuits and bonding require a project calculation.

Longitudinal water blocking and three single-core circuits

Swellable components limit water movement along the cable after moisture enters. They do not repair sheath damage or establish a separate radial moisture barrier. Water-blocked conductors, radial barriers and immersion conditions require their own construction and evidence.

Обозначения 3×1×240 describes three individually sheathed single-core cables, each with a 240 mm² conductor. It is not a three-core assembly. Drum allocation, шипы, cable entries and screen connections follow that distinction.

Diagram distinguishing water movement along a cable from radial entry through its sheath
Longitudinal blocking and a radial barrier address different moisture paths.
Three separate single-core aluminium cable cross-sections explaining the notation 3 x 1 х 240
Three single-core cables remain three individually sheathed products, even when installed together.

Applications and Installation Conditions

Utility distribution, transformer-substation connections and industrial feeders are typical fixed-installation contexts. Механическая защита, тепловой расчет, end sealing and aluminium-compatible connections remain part of the cable system. Ordinary PE sheath is not a substitute for a specified flame-retardant or LSZH design.

Сопротивление, partial-discharge and voltage-test records do not replace evidence for longitudinal water penetration or sheath integrity. The declared water-blocking construction and its test scope must agree. The official IEC scope provides standard context, not a VDE certificate or utility approval.

NA2XS(Ф)2Y and Related Constructions

МодельMain difference
Кабель NA2XSYAluminium conductor and PVC outer sheath instead of PE; longitudinal water blocking is not specified by the NA2XSY designation.
Кабель N2XS2YCopper conductor instead of aluminium, with XLPE insulation and a PE sheath; longitudinal water blocking is not specified by the N2XS2Y designation.
NA2XS(Флорида)2ДаAdds a laminated metallic moisture barrier beneath the PE sheath, providing radial moisture protection in addition to longitudinal water blocking.

NA2XS(Ф)2Y-кабель: часто задаваемые вопросы

Что значит (Ф) mean in NA2XS(Ф)2Да?

It identifies longitudinal water blocking. The exact tape arrangement and tested scope follow the declared construction; it does not by itself specify a radial barrier or a water-blocked conductor.

Does an aluminium conductor mean an aluminium screen?

Нет. The reference uses an aluminium phase conductor and a copper wire metallic screen. Screen area follows earth-fault duty and bonding requirements.

Is 3×1×240 the same as a three-core cable?

Нет. It is three separate single-core cables. A three-core cable contains the three phase cores inside one common sheath.