If you source low-voltage power cables for EU or Eurasian construction projects, you have likely encountered the N2XOH cable as a top recommended option. Unlike general-purpose PVC cables, this product is purpose-built to meet strict regional safety and performance requirements. 결과적으로, it is a reliable choice for projects that demand compliance, 내구성, and low fire hazard risk in high-occupancy environments.

In this guide, we cover the full technical specifications of N2XOH cable, its core structural features, ideal application scenarios, available sizes, and installation limitations — so you can make a fully informed sourcing decision.
N2XOH Cable Complete Specifications
| 목 | Specification |
|---|---|
| 케이블 유형 | N2XOH Halogen Free Power Cable |
| Conductor Material | Soft annealed copper |
| Conductor Class | 수업 2 / 수업 5 IEC 60228 |
| Conductor Structure | Compact stranded |
| 격리 | XLPE |
| 외부 칼집 | Halogen-free thermoplastic compound |
| Flame Property | Low smoke, halogen free, fire resistant |
| 기준 | IEC 60754-1, IEC 60287 |
Common Cross Section Size Parameters
| Cross Section (mm²) | Conductor Diameter (mm) | Overall Outer Diameter (mm) | Approximate Weight (kg/km) |
|---|---|---|---|
| 1.5 | 1.8 | 4.2 | 42 |
| 2.5 | 2.3 | 4.8 | 58 |
| 4 | 2.9 | 5.5 | 79 |
| 6 | 3.4 | 6.1 | 103 |
| 10 | 4.2 | 7.0 | 142 |
| 16 | 4.6 | 8.0 | 183 |
| 25 | 5.8 | 9.2 | 260 |
| 35 | 6.8 | 10.3 | 345 |
| 50 | 8.0 | 11.6 | 458 |
| 70 | 9.4 | 13.2 | 620 |
| 95 | 11.0 | 15.0 | 815 |
| 120 | 12.4 | 16.5 | 1020 |
What Makes N2XOH Cable EU-Standard Compliant?
N2XOH cable falls under the EU’s unified low-smoke zero-halogen (LSZH) cable category and fully complies with the EN50525-2-11 European standard for low-voltage power cables. 뿐만 아니라, it carries mandatory CE marking for EU markets and EAC certification for Eurasian Union regions — ensuring you avoid non-compliance delays during project inspections or customs clearance.
Its rated voltage of 0.6/1kV matches the requirements of most low-voltage power distribution systems. In addition, this voltage rating means the cable works seamlessly for general power supply tasks in commercial and industrial settings without requiring additional voltage derating.
Core Structural Features of N2XOH Cable
지휘자: 수업 2/5 구리
The conductor uses multi-strand bare copper meeting IEC 60228 수업 2/5 표준.
Insulation Layer: 90°C XLPE
The insulation uses 가교 폴리에틸렌 (XLPE) with a continuous operating temperature rating of 90℃. Compared to standard PVC insulation, which is typically rated at 70°C, XLPE provides significantly more stable performance during prolonged high-load operation. 결과적으로, the risk of insulation softening, short circuits, or electrical faults under sustained load is considerably reduced — an important advantage in commercial buildings with heavy and continuous power demand.
외부 칼집: LSZH Flame-Retardant Material
The outer sheath uses low-smoke zero-halogen (LSZH) flame-retardant compound, typically black for outdoor UV resistance. In the event of a fire, this sheath releases very little smoke and produces no toxic halogen gases. This is a critical safety advantage in high-occupancy spaces such as offices, shopping centres, and hospitals, where smoke inhalation and corrosive gas damage to electronics are primary concerns during fire incidents.
핵심 식별
By default, N2XOH cable uses black core wires with white numerical coding for straightforward installation and fault tracing. 추가적으로, custom versions with dedicated earth marking wires are available to match specific project wiring standards or local regulatory requirements.
Ideal Application Scenarios for N2XOH Cable
N2XOH cable is designed for 고정 설치 and performs reliably across three core environments: indoor spaces, outdoor covered areas, and embedded in concrete.
Commercial and High-Occupancy Buildings
N2XOH is the first choice for power wiring in office buildings, 쇼핑몰, hotels, and hospitals. In these environments, dense foot traffic and high-value equipment make LSZH fire performance a regulatory and practical requirement. The cable’s EN50525-2-11 compliance satisfies EU building regulations for cables installed in escape routes and occupied spaces. Moreover, the 90°C XLPE insulation supports the sustained load cycles typical in commercial buildings with round-the-clock operation.
Industrial Facilities
In factories, manufacturing plants, and industrial warehouses, N2XOH is commonly used for internal power distribution runs — from main distribution boards to sub-distribution panels, 모터, and fixed equipment. Its LSZH sheath meets the fire safety requirements increasingly required by industrial insurers and local building authorities.
Embedded and Concrete-Cast Installation
N2XOH is also approved for direct embedding in concrete — for example, in underfloor or wall-embedded power runs in commercial construction. 하지만, this application requires correct conduit or protective duct installation around the cable where mechanical damage during construction is possible.
Installation Limitations to Note
N2XOH cable is not suitable for all installation environments, and understanding its limitations prevents costly specification errors.
첫 번째, the cable is not rated for direct burial underground. Without armour protection, it cannot withstand the crush pressure, moisture exposure, and root penetration that direct-burial applications require. For underground runs, 에이 steel wire armoured (SWA) or aluminium wire armoured (아와) cable to IEC 60502-1 is the appropriate specification.
Second, N2XOH is not suitable for continuous immersion in water or permanently wet underground environments.
Third, ~을 위한 outdoor exposed installation, the cable requires additional mechanical protection against direct sunlight UV degradation and physical impact. Although the standard black sheath provides some UV resistance, prolonged unprotected outdoor exposure is not within the cable’s rated installation category.
Common N2XOH Cable Sizes and Technical Specifications
N2XOH cable is available in both single-core and multi-core configurations. Popular stock sizes include 1×16mm², 1×185mm², 1×240mm², and 4×16mm². For larger high-load applications, 1×300mm² variants are also available.
The following specifications apply to the most commonly sourced large single-core sizes.
1×185mm² N2XOH has a nominal outer diameter of 25mm and an approximate weight of 1,910kg per kilometre. This size is widely used for main feeder runs in medium-scale commercial buildings and industrial sub-distribution.
1×240mm² N2XOH has a nominal outer diameter of 28mm and an approximate weight of 2,370kg per kilometre. It is one of the most commonly specified sizes for main LV incoming feeders in large commercial buildings and distribution substations.
1×300mm² N2XOH has a nominal outer diameter of 30mm and an approximate weight of 2,970kg per kilometre. This is the largest standard single-core size and is typically used for high-current main feeder applications where copper conductor size is preferred over aluminium for space-constrained cable routes.
These specifications allow you to calculate conduit size requirements, cable tray load limits, and transportation weight constraints accurately during project planning.
About XWA Power — N2XOH and LSZH Cable Manufacturer
XWA 전력 주식회사, 주식회사. manufactures N2XOH and a full range of EN-standard LSZH low-voltage cables from our 33,000m² factory in Xiangcheng, 허난성, 중국. Our cables comply with EN50525-2-11, IEC 60502-1, IEC 60228, and BS 7211 표준, and carry CE and EAC certification for EU and Eurasian markets.
All cable drums undergo 100% per-metre electrical testing before shipment, including conductor resistance, 절연저항, and high-voltage withstand tests. ISO 9001 이후 인증 2007. 다음으로 내보내기 60+ countries across Europe, 중동, 아프리카, and Asia.
자주 묻는 질문
1. What European standard does N2XOH cable comply with? N2XOH cable fully complies with EN50525-2-11, the European standard for low-voltage power cables with LSZH insulation and sheath. In addition, it carries CE marking for EU markets and EAC certification for Eurasian Union regions — both of which are required for project compliance in these markets.
2. Is N2XOH cable suitable for direct burial underground? 아니요. N2XOH cable is not rated for direct burial or continuous immersion in water. It lacks the mechanical armour protection required to withstand soil pressure, moisture ingress, and root penetration in underground environments. For direct burial applications, a steel wire armoured cable to IEC 60502-1 is the correct specification instead.
3. What is the temperature rating of N2XOH cable’s XLPE insulation? The XLPE insulation of N2XOH cable has a continuous operating temperature rating of 90°C. This is significantly higher than standard PVC insulation, which is typically rated at 70°C. 결과적으로, N2XOH maintains stable electrical performance during sustained high-load operation — an important advantage in commercial buildings with round-the-clock power demand.
4. Why is N2XOH cable recommended for shopping malls and office buildings? N2XOH uses an LSZH outer sheath that releases minimal smoke and no toxic halogen gases during a fire. This directly reduces the risk of smoke inhalation injury to building occupants and corrosive gas damage to high-value electronic equipment. 뿐만 아니라, its EN50525-2-11 compliance satisfies EU building regulations for cables installed in escape routes and occupied spaces.
5. What is the weight of 1×240mm² N2XOH cable per kilometre? A 1×240mm² N2XOH cable has an approximate weight of 2,370kg per kilometre and a nominal outer diameter of 28mm. These values are used to calculate cable tray load ratings, conduit fill requirements, and transportation logistics during project planning.
6. What conductor class does N2XOH cable use, and why does it matter? N2XOH uses a Class 2/5 copper conductor to IEC 60228.